3-136 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF PIDRegFPID#.DeltaOut.db R/W/C
zeroDb INT32U CF 0 R
Spt MV PID # Setpoint value R
instMag AnalogueValue MX R
instMag.f FLOAT32 PID # Setpoint R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF PIDRegFPID#.Spt.db R/W/C
zeroDb INT32U CF 0 R
PIDAlg ENG Algorithm, which is fixed at PID R
setVal ENUMERATED SP 7, the code for PID R
KP ASG PID # PROPORTIONAL GAIN setting R
setMag AnalogueValue SP R
setMag.i INT32 PID # PROPORTIONAL GAIN R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
sVC ScaledValue
Config
CF R
sVC.scaleFactor FLOAT32 1/100 R
sVC.offset FLOAT32 0 R
KI ASG PID # Integral gain value R
setMag AnalogueValue SP R
setMag.i INT32 PID # PROPORTIONAL GAIN R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
sVC ScaledValue
Config
CF R
sVC.scaleFactor FLOAT32 1/100 R
sVC.offset FLOAT32 0 R
ITmms ING PID # INTEG. TIME CONST. setting in
milliseconds
R
setVal INT32 SP PID # INTEG. TIME CONST. scaled
to make the result in
milliseconds
R
minVal INT32 CF 0 R
maxVal INT32 CF 600,000 R
stepSize INT32 CF 10 R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for time in seconds R
units.multiplier ENUMERATED -3, the code for a multiplier of 0.001 (i.e.
Milli)
R
KD ASG PID # Derivative gain value R
setMag AnalogueValue SP R
LNName: PIDRegFPID# LDevice inst: Ctrl UR element: PID Regulator element #
data obj. data attribute Type FC UR Name Description R/W/C