CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-137
3
3.5.3.20 Reduced voltage starting (LoVStr)
This element is instantiated in the following products: M60.
Table 3-157: Reduced voltage starting data objects
setMag.i INT32 PID # PROPORTIONAL GAIN R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
sVC ScaledValue
Config
CF R
sVC.scaleFactor FLOAT32 1/100 R
sVC.offset FLOAT32 0 R
DTmms ING PID # DERIV. TIME CONST. setting in
milliseconds
R
setVal INT32 SP PID # DERIV. TIME CONST. scaled
to make the result in
milliseconds
R
minVal INT32 CF 0 R
maxVal INT32 CF 600,000 R
stepSize INT32 CF 10 R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for time in seconds R
units.multiplier ENUMERATED -3, the code for a multiplier of 0.001 (i.e.
Milli)
R
DFilTmms ING PID # Derivative filter time setting in
milliseconds, which is the ratio of
derivative time constant to derivative
limit
R
setVal INT32 SP (PID # DERIV. TIME CONST.
divided by PID # DERIVATIVE
LIMIT) scaled to make the result
in milliseconds
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for time in seconds R
units.multiplier ENUMERATED -3, the code for a multiplier of 0.001 (i.e.
Milli)
R
InRef1 ORG PID # PROCESS SIGNAL setting R
setSrcRef ObjectReference SP PID # PROCESS SIGNAL setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG PID # TRACKING SIGNAL setting. R
setSrcRef ObjectReference SP PID # TRACKING SIGNAL setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG PID # BLK setting. R
setSrcRef ObjectReference SP PID # BLK reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: LoVStrGAPC1 LDevice inst: Ctrl UR element: REDUCED VOLTAGE STARTING element
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD Mandatory data object which in this case
is fixed at false
R
LNName: PIDRegFPID# LDevice inst: Ctrl UR element: PID Regulator element #
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents