3-140 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
ShotCnt4 SPS AR SHOT CNT=4 operand R
stVal BOOLEAN ST AR SHOT CNT=4 R
ArMod1 SPS AR MODE = 1 operand R
stVal BOOLEAN ST AR MODE = 1 R
ArMod2 SPS AR MODE = 2 operand R
stVal BOOLEAN ST AR MODE = 2 R
ArMod3 SPS AR MODE = 3 operand R
stVal BOOLEAN ST AR MODE = 3 R
ArMod4 SPS AR MODE = 4 operand R
stVal BOOLEAN ST AR MODE = 4 R
SwFail SPS AR MODE SWITCH FAIL operand R
stVal BOOLEAN ST AR MODE SWITCH FAIL R
Zn1Extend SPS AR ZONE 1 EXTENT operand R
stVal BOOLEAN ST AR ZONE1 EXTENT R
SeqTO SPS AR INCOMPLETE SEQ operand R
stVal BOOLEAN ST AR INCOMPLETE SEQ R
Rs SPS AR RESET operand R
stVal BOOLEAN ST AR RESET R
InRef01 ORG Mode 1 Activation setting R
setSrcRef ObjectReference SP AR Mode 1 Activation setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef02 ORG Mode 2 Activation setting R
setSrcRef ObjectReference SP AR Mode 2 Activation setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef03 ORG Mode 3 Activation setting R
setSrcRef ObjectReference SP AR Mode 3 Activation setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef04 ORG Mode 4 Activation setting R
setSrcRef ObjectReference SP AR Mode 4 Activation setting reference to the data attribute to input R
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R
BlkRef2 ORG AR BLOCK BKR1 setting R
setSrcRef ObjectReference SP AR BLOCK BKR 1 setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef06 ORG AR BKR MAN CLOSE setting R
setSrcRef ObjectReference SP AR BKR MAN CLOSE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef07 ORG AR 1P INIT setting R
setSrcRef ObjectReference SP AR 1P INIT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef08 ORG AR 3P INIT setting R
setSrcRef ObjectReference SP AR 3P INIT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef09 ORG AR 3P TD INIT setting R
setSrcRef ObjectReference SP AR 3P TD INIT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef10 ORG AR MULTI-P FAULT setting R
setSrcRef ObjectReference SP AR MULTI-P FAULT setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef11 ORG BKR ONE POLE OPEN setting R
LNName: Rec13pRREC1 LDevice inst: Ctrl UR element: Autoreclose element
data obj. data attribute Type FC UR Name Description R/W/C