3-148 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.28 Transformer hottest spot temperature (HPTmp)
This element is instantiated in the following products: G30, T35, T60.
Table 3-165: Hottest spot temperature data objects
3.5.3.29 Transformer loss of life (LosLif)
This element is instantiated in the following products: G30, T35, T60.
Table 3-166: Transformer loss of life data objects
LNName: HPTmpSPTR1 LDevice inst: Ctrl UR element: Hottest-Spot Temperature Function
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT XFMR HST-SPOT ˚C OP R
general BOOLEAN ST XFMR HST-SPOT ˚C OP R
Dpo SPS XFMR HST-SPOT °C DPO operand R
stVal BOOLEAN ST XFMR HST-SPOT °C DPO R
Str ACD XFMR HST-SPOT °C PKP operand R
general BOOLEAN ST XFMR HST-SPOT °C PKP R
dirGeneral ENUMERATED ST 0 R
ToOilTmp MV TOP OIL °C actual Value R
instMag AnalogueValue MX R
instMag.f FLOAT32 TOP OIL °C R
mag Analogue Value MX R
mag.f FLOAT32 instMag.i on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 23, the code for °C R
units.multiplier ENUMERATED 0 is code for a multiplier 1 R
db INT32U CF HPTmpSPTR1.ToOilTmp.db R/W/C
zeroDb INT32U CF 0 R
HPTmpClc MV HOTTEST-SPOT ° C actual values R
instMag AnalogueValue MX R
instMag.f FLOAT32 HOTTEST-SPOT ° C R
mag Analogue Value MX R
mag.f FLOAT32 instMag.i on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 23, the code for °C R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF HPTmpSPTR1.HPTmpClc.db R/W/C
zeroDb INT32U CF 0 R
BlkRefγ ORG XFMR HST BLOCK for setting group γ R
setSrcRef ObjectReference SP XFMR HST BLOCK for group γ Reference to the data attribute to input R/C
setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/C
LNName: LosLifSPTR1 LDevice inst: Ctrl UR element: Loss of Life Function
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT XFMR LIFE LOST OP operands R
general BOOLEAN ST XFMR LIFE LOST OP R
Str ACD XFMR LIFE LOST PKP operand R
general BOOLEAN ST XFMR LIFE LOST PKP R
dirGeneral ENUMERATED ST 0 R
LosLifeRte MV DAILY RATE LOL actual Values. R
instMag AnalogueValue MX R