OPM_LPS_33E_10K_30K_4CN_V010.doc 55/82 Operating Manual LP 33 / 10-20-30 kVA
Example 4: If the IEM mode must be enabled on Monday and Tuesday between 18:00 in the
evening and 06:00 of the following morning, on Friday between 12:00 and 13:00,
during all Saturday and on Sunday until 20:00, the corresponding parameters are.
Weekday
Saturday Sunday Monday Tuesday Wednesday Thursday Friday
IEM START
00:00 00:00 18:00 18:00 00:00 00:00 12:00
IEM STOP
23:59 20:00 23:59 06:00 06:00 00:00 13:00
IEM START
IEM STOP
In dark colour are displayed the times with IEM mode operation.
The arrows indicate the conditions given by the IEM START and IEM STOP times introduced with
the parameters.
Note that on day Tuesday the interval has length 0 (zero), therefore the IEM mode is not enabled
on this day.
Example 5: An equivalent set of parameters for Example 4 is.
Weekday
Saturday Sunday Monday Tuesday Wednesday Thursday Friday
IEM START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
IEM STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
IEM START
IEM STOP
The IEM mode is active from 18:00 of weekday Monday until 06:00 of weekday Tuesday (as
indicated by the IEM STOP time of weekday Tuesday).
The IEM STOP time of weekday Monday has no effect as it is followed by the IEM STOP time of
weekday Tuesday.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the IEM mode is active from 18:00 of weekday Tuesday until 06:00 of weekday
Wednesday.
The IEM START time of weekday Wednesday has no effect as it is preceded by the IEM START
time of weekday Tuesday.
It can be, without change of meaning, any time between 00:00 and 06:00.
To avoid undesired IEM mode operation, verify:
• Date and Time (first page of parameter).
• IEM mode screen how many hours of IEM mode operation have been
selected for each day of the week.
NOTE !
The IEM mode becomes active only if the load is supplied from inverter.