OPM_LPS_33E_10K_30K_4CN_V010.doc 59/82 Operating Manual LP 33 / 10-20-30 kVA
> INVERTER ON ٭
INVERTER OFF
6. In order to discharge the DC link capacitors, start once
more the inverter through the screen:
MENU/COMMAND MENU/INVERTER ON
Inverter: U1= 7V
U2= 7V U3= 7V
Remark: command INVERTER ON will be enabled only
when the inverter voltage of each phase
decreases below 7 VAC (about 30 seconds).
Udc Voltage
Udcp= 5V Udcn= 5V
Before proceeding to step 7, check on the display panel that
the DC link voltage (both polarities) Udcp and Udcn has
reached the minimum voltage of 5 VDC (about 30 seconds).
INVERTER ON
> INVERTER OFF ٭
7. Switch OFF the inverter by entering the screen:
MENU/COMMAND MENU/INVERTER OFF
Attention: to switch OFF permanently the inverter the ke
Enter must be pressed 2 times.
The load is now powered directly by mains through the manual bypass Q2.
WARNING !
The UPS cabinet contains parts electrically live.
Apart from the front door, do not open any other part of the UPS.
NOTE !
With separate mains inputs, it’s possible to disconnect mains rectifier.