OPM_LPS_33E_10K_30K_4CN_V010.doc 61/82 Operating Manual LP 33 / 10-20-30 kVA
bypass Q2 (Pos.
0).
Verify, selecting the
screen
METERING/Udcp
and Udcn, that the
booster voltage has
reached about 400
VDC.
5. Switch ON the
inverter by entering
the screen:
MENU/COMMAND
MENU/INVERTER
ON
> INVERTER ON ٭
INVERTER OFF
Some seconds later
the load will be
transferred on
inverter and the
main screen will
display:
APPLICATION ON
UPS
LP 33 20kVA
APPLICATION ON UPS