DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 3. EntelliGuard TU Trip Unit System
©2012 General Electric All Rights Reserved
Table 3.3. Selectivity with EntelliGuard TU Trip Units in ANSI and ICCB/ Power Break II Circuit Breakers
Downstream device with
EntelliGuard TU Trip Unit
Power Break II,
UL 489 CB
EntelliGuard G,
ANSI/UL Std I
EntelliGuard
G, ANSI Ext I
Frame determines
maximum
instantaneous
pickup (X) for PB II
and WP CB.
Plug/Icw ratio
determines
maximum possible
for EntelliGuard
GCB. EntelliGuard
values shown are
more maximum
withstand tiers.
6000A frame
(UL 489 only)
Amperes per above multipliers
1600A frame,
24,000
24,000
24,000
48,000
3000A frame,
39,000
N/A 45,000
90,000
4000A frame,
40,000
40,000
60,000
92,000
6000A frame,
N/A N/A 90,000
N/A
• Maximum instantaneous is a multiple of rating plug. The above values may be lower if a smaller rating plug than maximum for frame is used. In PB II &
WavePro circuit breakers, the maximum instantaneous multiplier is limited by frame rating. In EntelliGuard G, the maximum Instantaneous X may be
limited by circuit breaker withstand or short time rating (also known as Icw). The current numbers above multiplied by 0.9 provide maximum selectivity
above non-current limiting if instantaneous is adjusted to maximum and no zone selective interlocking is used.
Note: For complete listing of all selectivity functionalities see publication DET-537D