DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
Digits 16 & 17 – Overcurrent Protection Package
Over Current (OC) Protection Package
EntelliGuard G
ANSI/UL OC
Protection with
Fuse Settings
Standard Range
Instantaneous
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (G, Alarm Only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (C, Alarm Only)
(S, G, A switchable) (I, switchable ANSI only)
(S, G, C, A all switchable) (I, switchable ANSI only)
Extended Range
Adjustable
Instantaneous
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (G, Alarm Only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (C, Alarm Only)
(S, G, A switchable) (I, switchable ANSI only)
(S, G, C, A all switchable) (I, switchable ANSI only)
EntelliGuard G
ANSI/UL OC
Protection with
Fuse Settings
FROM 1/1/12:
INCLUDED IN L
TYPE TRIP
UNITS
Standard Range
Instantaneous
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (G, Alarm Only)
(S, switchable) (I, switchable ANSI only)
(S, switchable) (I, switchable ANSI only) (C, Alarm Only)
JSIGDA* (S, G, A all switchable) (I, switchable ANSI only)
(S, G, C, A all switchable) (I, switchable ANSI only)
Extended Range
Adjustable
Instantaneous
(S, switchable) (H, switchable ANSI only)
(S, switchable) (H, switchable ANSI only)
(S, switchable) (H, switchable ANSI only) (G, Alarm Only)
(S, switchable) (H, switchable ANSI only)
(S, switchable) (H, switchable ANSI only) (C, Alarm Only)
(S, G, A all switchable) (H, switchable ANSI only)
(S, G, C, A all switchable) (H, switchable ANSI only)
NONE - (For Switch Only)
= Ground Fault, External Ground Fault, Alarm only
= External CT for ground fault detection (AKD20 application: input from external summing CTs, used for multiple source ground fault detection. OEM
application: Zero Sequence Input of 1A = 100%)
= Defeatable/Switchable Ground Fault, not UL Listed
= Ground Fault Protection (GFP, 3-wire or 4-wire, internal summing)
= Extended Range Adjustable Instantaneous, (IOC, 2x-30x), not available in UL489 version of EntelliGuard G or any Legacy CB
= Standard Range Adjustable Instantaneous, (IOC, 2x-15x)
= Long Time (L, I
2
T) + Fuse Settings (I4T)
= Long Time (I
2
T, all trip unit)
= Short Time (Switchable if Instantaneous (I) protection is enabled)
= External Ground Fault Alarm Only
= Ground Fault Alarm Only
GDA, GCDA = Ground Fault Trip and Ground Fault Alarm (all switchable, not UL Listed)
*Function Combination is NOT UL Listed.
• Option "XX" is the only valid option when a Switch is selected in Digit 2.