DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
Digit 5 – Cassette Envelope Size
Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB
65,000 65,000 50,000 50,000 50,000 49,000 53,500
X
100,000 100,000 65,000 65,000 65,000 63,700 69,550
X
100,000 100,000 100,000 100,000 none none none
X X
Interrupting Rating Tier UL489 Devices ICCB
ANSI Non-Automatic Switches
30 Cycle Withstand Ratings
Notes: Non-automatic switches are provided
with no internal sensing or tripping mechanism
and cannot be applied above their respective
withstand levels. If a non-automatic device is
required at ratings above the available
switches is required, it is recommended that a
circuit breaker set with maximum settings be
employed using external control or protection
as required by the application.
UL489 Non-Automatic Switches
Digit 6 - Cassette Type & Number of Poles
OEM Cassette – 3 Pole
OEM Cassette – 4 Pole
GE Equipment Cassette – 3 Pole**
* P version available only in 3 pole.
** GE Equipment cassette designed specifically for AKD20 Switchgear.
These cassettes are NOT available for OEMs.
Shutter and Shutter Lock - Factory Installed
Loose Cassette Parts – Field Installed
Carriage Position Switch - 1 NO/1NC
Carriage Position Switch - 2 NO/2NC
1 Kirk Key Interlock Cam for Cassette
1 Ronis Key Interlock Cam for Cassette
Secondary Disconnect Block B, 39 Pole - Top
Secondary Disconnect Block B, 39 Pole - Side
• Secondary Disconnect Block B is required when:
- Any "Z
ONE SELECTIVE INTERLOCKING" options are selected in
breaker/trip unit Catalog Digit 18.
- An
y "ADVANCED FEATURES" are selected in breaker/trip unit Catalog
Digit 19.
- A COIL SIGNALING CONTACT OPTION is selected, Digit 12.
- A R
EADY TO CLOSE signal via the trip unit is selected, Digit 13.
- An
y of the following OPTIONAL Aux. Contact Switches are selected in
Digit 12:
8NO
/NC POWER RATED
3NO/NC POWER RATED + 2NO/NC Hi-Fi
4NO/NC POWER RATED + 4NO/NC Hi-Fi