DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
69
Digit 5 Cassette Envelope Size
Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB
Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
1/2S
Withstand
HSIOC
Override
No. 1
Override
WI
400-2000
3200
400-
3200
3200
4000-
5000
S
65,000 65,000 50,000 50,000 50,000 49,000 53,500
S
X
N
65,000
65,000
65,000
65,000
none
none
none
N
X
X
H
85,000
85,000
65,000
65,000
65,000
63,700
69,500
H
X
P*
100,000 100,000 65,000 65,000 65,000 63,700 69,550
P
X
E
85,000
85,000
85,000
85,000
none
none
None
E
X
M
100,000
100,000
85,000
85,000
85,000
83,800
90,950
M
X
Use B
B
100,000 100,000 100,000 100,000 none none none
B
X X
L
150,000
150,000
100,000
100,000
100,000
98,000
107,000
L
X
X
Interrupting Rating Tier UL489 Devices ICCB
Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
1/2S
Withstand
HSIOC
Override
No. 1
Override
WI
400-2000
2500-
3000
400-
3000
3000
4000
5000-
6000
S
65,000
65,000
50,000
42,000
42,000
N/A
44,940
S
X
N
65,000
65,000
65,000
42,000
42,000
N/A
44,940
N
X
X
H
85,000
85,000
65,000
50,000
50,000
N/A
53,500
H
X
X
P*
100,000
100,000
65,000
50,000
50,000
N/A
53,500
P
X
M
100,000
100,000
85,000
65,000
65,000
N/A
69,550
M
X
X
Use L
L
150,000
150,000
100,000
85,000
85,000
N/A
90,950
L
X
X
X
ANSI Non-Automatic Switches
30 Cycle Withstand Ratings
Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
Notes: Non-automatic switches are provided
with no internal sensing or tripping mechanism
and cannot be applied above their respective
withstand levels. If a non-automatic device is
required at ratings above the available
switches is required, it is recommended that a
circuit breaker set with maximum settings be
employed using external control or protection
as required by the application.
800-2000
800-3200
3200-5000
N
42,000
42,000
42,000
N
X
M
65,000
65,000
65,000
M
X
B
100,000
100,000
100,000
B
X
UL489 Non-Automatic Switches
Envelope 1
Envelope 2
Envelope 3
240V
480V
600V
800-2000
800-3000
3000-6000
N
42,000
42,000
42,000
N
X
M
65,000
65,000
65,000
M
X
B
100,000
100,000
100,000
B
X
Digit 6 - Cassette Type & Number of Poles
Device Series/Line
Code
OEM Cassette 3 Pole
2
OEM Cassette 4 Pole
5
GE Equipment Cassette 3 Pole**
7
* P version available only in 3 pole.
** GE Equipment cassette designed specifically for AKD20 Switchgear.
These cassettes are NOT available for OEMs.
Digit 7 - Shutter
Shutters with Locks
Code
Shutter and Shutter Lock - Factory Installed
S
None
X
Loose Cassette Parts Field Installed
Carriage Position Switch - 1 NO/1NC
GCPS1R
Carriage Position Switch - 2 NO/2NC
GCPS2R
1 Kirk Key Interlock Cam for Cassette
GCKRKR
1 Ronis Key Interlock Cam for Cassette
GCRONR
Secondary Disconnect Block B, 39 Pole - Top
Mounted
GSDWTR
Secondary Disconnect Block B, 39 Pole - Side
Mounted
GSDWSR
Secondary Disconnect Block B is required when:
- Any "Z
ONE SELECTIVE INTERLOCKING" options are selected in
breaker/trip unit Catalog Digit 18.
- An
y "ADVANCED FEATURES" are selected in breaker/trip unit Catalog
Digit 19.
- A COIL SIGNALING CONTACT OPTION is selected, Digit 12.
- A R
EADY TO CLOSE signal via the trip unit is selected, Digit 13.
- An
y of the following OPTIONAL Aux. Contact Switches are selected in
Digit 12:
8NO
/NC POWER RATED
3NO/NC POWER RATED + 2NO/NC Hi-Fi
4NO/NC POWER RATED + 4NO/NC Hi-Fi