GE EntelliGuard G - Typical Connection Arrangement

GE EntelliGuard G
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EntelliGuard G
BREAKER
INSTALLATION
1.3
1.3-05
Breaker terminal
Tomadas Disjuntor
Toma interruptor
Customer bus
Barramento Exterior
Embarrado exterior
Customer bus
Barramento Exterior
Embarrado exterior
Hex Nut (8.8)
Porca Sextavada (8.8)
Tuerca Hex (8.8)
Hex Bolt (8.8)
Parafuso Sextavado (8.8)
Tornillo Hex. (8.8)
Lock Washer
Anilha de Segurança
Arandela de seguridad
Plain Washer (Heavy duty)
Anilha plana (alta resistência)
Arandela plana (alta resistencia)
1.3.4: Typical Connection Arrangement
1.3.4: Ligação Típica Tomadas Standard
1.3.4: Conexionado típico Tomas estándar
Breaker type 'Automatic' Switch Type Envelope In (A) Recommended Copper Bus Bar sizes
----------------------------------------------------------------------------------------------------- -----------------------------
GG04, S N & H GJ04S & GW04N 1 or/ó 2 400 1 x 40 x 10 or 1 x 80 x 5 or 2 x 40 x 5
GG04 E & M GJ04H 1 or 2 400 1 x 40 x 10 or 1 x 80 x 5 or 2 x 40 x 5
GG07, S N & H GJ07S & GW07N 1 or 2 630 1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
GG07 E & M GJ07H 1 or 2 630 1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
GG08, S N & H GJ08S & GW08N 1 or 2 800 1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
GG08 E & M GJ08H 1 or 2 800 1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
GG10, S N & H GJ10S & GW10N 1 or 2 1000 1 x 60 x 10 or 2 x 60 x 5
GG10 E & M GJ10H 1 or 2 1000 1 x 60 x 10 or 2 x 60 x 5
GG13, S N & H GJ13S & GW13N 1 or 2 1250 2 x 40 x 10 or 2 x 80 x 5
GG13 E & M GJ13H 1 or 2 1250 2 x 40 x 10 or 2 x 80 x 5
GG16, S N & H GJ16S & GW16N 1 1600 2 x 50 x 10 or 2 x 100 x 5
GG16 E & M GJ16H 2 1600 2 x 50 x 10 or 2 x 100 x 5
GG20, S N & H GJ20S & GW20N 1 2000 3 x 50 x 10 or 3 x 100 x 5
GG20 E & M GJ20H 2 2000 3 x 50 x 10 or 3 x 100 x 5
GG25N, H & M GJ25N & GW25H 2 2500 4 x 50 x 10 or 4 x 100 x 5
GG32N, H & M GJ32N & GW32H 2 or 3 3200 4 x 100 x 10
GH32N, H & M GK32N & GZ32H 2 or 3 3200 4 x 100 x 10
GG32G & L GJ32G 2 or 3 3200 4 x 100 x 10
GG40N, H & M GJ40N & GW40H 2 4000 4 x 100 x 10 + 1 x 100 x 5
GH40N, H & M GK40N & GZ40H 2 4000 4 x 100 x 10 + 1 x 100 x 5
GG40G & L GJ40G 3 4000 4 x 100 x 10
GG50M & L CJ50L 3 5000 5 x 120 x 10 or 6 x 100 x 10
GG64M & L CJ64L 3 6400 7 x 120 x 10 or 8 x 100 x 10
Disjuntor Interruptor de corte em carga Tamanho In (A) Tamanhos recomendados de barra de cobre
Interruptor automático Interruptor en carga Tamaño In (A) Tamaños recomendados de barra de cobre
[or = ou = ó]
Recommended Connection Cross
sections
The adjacent table indicates the
recommended bus bar dimensions
to be used in connecting the
EntelliGuard G™ Power Circuit
Breaker.
Secções de ligação
recomendadas
A tabela adjacente indica as
dimensões recomendadas de
barra para serem usadas na
ligação do
Disjuntor EntelliGuard G™.
Secciones recomendadas
La tabla adjunta indica las
secciomes recomendadas de
las barras a utilizar para la
conexión del Interruptor de
bastidor EntelliGuard G™