EntelliGuard®TU Trip Unit
Appendix 1 – Communications Parameters 09/25/08
30 © 2008 General Electric All Rights Reserved
Register Variable Value Read/Write
2–2
…
13–13
14–14
15–15
267 Power Reversal Pickup 1–10
2–20
…
97–970
98–980
99–990
Read/Write
268 Power Reversal Delay 0–Off
1–1
2–2
…
13–13
14–14
15–15
Read/Write
269 Power Direction Setting 0–Line to Load
1–Load to Line
Read/Write
270 Power Demand Interval 1–5
2–10
…
5–15
12–60
Read/Write
271 Relay 1 (Output 1) Function 1–Group 1
2–Group 2
3–Group 3
4–Group 4
5–Group 5
6–Group 6
7–Group 7
Read/Write
272 Relay 2 (Output 2) Function 1–Group 1
2–Group 2
3–Group 3
4–Group 4
5–Group 5
6–Group 6
7–Group 7
Read/Write
273 Relay 3 (Output 3) Function 1–Group 1
2–Group 2
3–Group 3
4–Group 4
5–Group 5
6–Group 6
7–Group 7
Read/Write
274 Relay 4 (Output 4) Function 1–Group 1
2–Group 2
3–Group 3
4–Group 4
5–Group 5
6–Group 6
7–Group 7
Read/Write
275 Input 1 Function 0–None, 1–Trip Breaker, 2–Reduce Instantaneous Read/Write
276 Input 2 Function 0–None, 1–Trip Breaker Read/Write
277 Input 3 Function 0–None, 1–Trip Breaker Read/Write
278 Input 4 Function 0–None, 1–Trip Breaker Read/Write
285 Waveform Capture 0–Disable
1–Manual
2–Over Current
3–Protection Relays
4–Current Alarm 1
5–Current Alarm 2
6–All
Read/Write
286 Language 0–English, 1–French, 2–Spanish, 3–German, 4–Chinese Read/Write
287 Time Sync Year 8 bit Read/Write
288 Time Sync Month 8 bit Read/Write
289 Time Sync Date 8 bit Read/Write