EasyManua.ls Logo

GE Innova IGS 520 - 2.4 Cable Channeling; 2.4.1 General; 2.4.2 Conduit; 2.4.3 Electrical Ducts

GE Innova IGS 520
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.4 Cable Channeling
2.4.1 General
High voltage and power cables must be separated from other cables. Use a separate trough in
the duct system, or use a separate conduit. Minimize cable length between the line disconnect
and the System Cabinet power unit to reduce voltage regulation problems and wiring costs.
For information about the cables supplied with your system, please refer to Physical Runs.
2.4.2 Conduit
Separate conduits must be used for power and signal wires. These wires must be kept
separated from each other.
Using conduit imposes some important considerations when used with this system. Of primary
concern, the majority of cables used are pre–terminated. Pre–termination greatly simplifies
interconnection but makes cable–pulling difficult because of the added dimensions of the
connectors.
Conduit must be large enough to pass the cable and connector through with all other cables
already in the conduit. Also, the size of conduit chosen must allow for future growth. There is the
possibility of additional cables being added later as the system is developed and options are
added.
The use of conduit is recommended for cables running overhead between rooms, especially
when a diagonal run provides the shortest cable path
Separate conduits must be used for Hospital and Fluoro UPS power wires. These wires must be
kept separated from each other (at least 30 cm).
2.4.3 Electrical Ducts
NOTE: (For IVUS Rev 3 option) refer to Volcano s5i Imaging System Integration in IGS
Systems - Service Manual.
It’s important that electrical ducts have separate compartments for power and signal wires.
These wires must be kept separated from each other for proper system operation.
Electrical ducts have advantages, when used with a single room or two adjacent rooms.
Electrical ducts combine cabling in a neat and functional appearance, with accessibility and
room for expansion.
NOTE:
Medrad AVANTA, IVUS and Mac-lab cables exit behind the table in the patient room.
NOTE: For Fast Link cable (C1 cabinet - AW station), the static operation bending radius
must be at least 4 times the outer cable diameter.
It is the responsibility of the site planner to provide the appropriate solution to the table exit (e.g
gas box, Clab II, Tram module, connection interface box)
Innova
TM
IGS 520, Innova
TM
IGS 530, Innova
TM
IGS 540 Pre-Installation Manual
Direction 5499972-1-1EN, Revision 2
224 2 System Cable Information

Table of Contents

Related product manuals