WARNING
MEASUREMENTS SHOULD BE PERFORMED ON A SYSTEM OFF.
Large Display Monitor System special instructions:
WARNING
THERE IS A DANGER TO LIFE IF WARNINGS ARE NOT OBEYED. SEVERE PERSONAL
INJURY OR DAMAGE TO EQUIPMENT MAY OCCUR.
DO NOT INSERT ANY OBJECTS INTO THE HOUSING.
OBJECTS INSERTED INTO THE HOUSING MAY RESULT IN DAMAGE TO THE UNIT OR
PERSONAL INJURY. DO NOT PLACE ANY OBJECTS ON TOP OF THE LARGE DISPLAY
CABINET. LIQUID ENTERING THE UNIT MAY RESULT IN FIRE OR ELECTRIC SHOCK.
Backup power instructions:
The Large Display subsystem is powered by the Hospital mains single phase electrical power. It is not
supplied by the Fluoro UPS in case of power outage, but by its own 3kVA UPS.
Customer Requirements:
Large Display Option:
The customer shall provide the power supply cables between the transformer and the UPS of the LD
cabinet (for LD system option).
The LDM optional system must be powered through a wall circuit breaker or equivalent device with
LOTO capability. This circuit breaker must have a 30 amps current rating. Procurement, delivery and
installation of this device is customer responsibility.
The customer shall provide Power supply cables between the main transformer and the system:
Main supply: 3 phases + 1 ground (+ 1 neutral if Fluoro UPS option present)
Cables from PDB to Jedi (LAT and FRT)
Cables from PDB to Tube Chillers (LAT and FRT)
Cable from PDB to modular PDU inside C2 cabinet
Cable from PDB to the fluoro UPS
Injectors: If Injector is not powered by the PDB, it is the customer responsibility to ensure the
compliance of installation by referring to injector's documentation.
5.1.2 Power Distribution
NOTE
All short AC power cable less than 3 meters, between peripherals and respective power
strip, are not shown. All have a single phase line, a neutral line and a ground wire.
Electrical Requirements
140
Innova
TM
IGS 6
5750182-1EN 3

Table of Contents