MA-041 DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1 4-Mar-22 Page 81 of 99
Figure 10-12: Add / Remove Measurements Points > Tap Position & OLTC Motor Torque
12. Right click in the data area and select Export to CSV.
13. In the Export to CSV dialog box, browse to an appropriate location, type a suitable
filename and click Save.
The OLTC data is now saved externally to a CSV file format.
10.3.4 Generate Configuration Files
Use the Excel commissioning tool called ‘Commissioning_Document_v1.2’ to generate
the required OLTC configuration files. The spreadsheet takes the following inputs:
The tap position movements in the form of raw CSV data (as output by
Perception in Section 10.3.3)
The ‘through positions’ of the tap changer
This data is used to produce the tap position map and the motor torque configuration
files, output in the form of TapPositionCalibration.cfg, OltcGroups.cfg and
OltcRefData.cfg. To use the tool, perform the following steps:
1. Start Microsoft Excel and open the Commissioning_Document_v1.2 as shown in
Figure 10-13.