UPS Input / Output connection
Cable sections (European standard) Input / Output
10kVA 20kVA 30kVA
5 x 4 mm2 5 x 10 mm2 5 x 10 mm2
Use the eyelet terminals from the plastic bag, for the
connection of Neutrals and Earth to Input / Output.