GE Limitamp CR194 - Controller Operation; Operational Circuit Checks; Test Power Circuit Procedure; Pre-Operation Preparation

GE Limitamp CR194
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CR
194
Vacuum
Limitamp
400
Ampere
Control
Operation
General
A
test
-
power
interlock
(
TPI
)
(
See
Figure
14
)
circuit
and
Test
-
Normal
Selector
Switch
(
TSW
)
(
See
Figure
9
)
is
provided
to
check
out
the
control
circuit
of
the
complete
unit
without
applying
power
to
the
motor
.
After
all
control
-
circuit
connections
are
made
,
the
controller
should
be
put
through
its
complete
operating
sequence
,
in
the
test
position
,
as
a
final
check
.
A
wiring
diagram
which
shows
the
circuit
and
connections
that
apply
to
the
controller
is
included
with
the
controller
when
it
is
shipped
from
the
factory
.
All
external
wiring
from
the
controller
must
be
made
in
accordance
with
the
connection
diagram
supplied
with
the
controller
.
make
a
good
contact
when
closed
.
The
relay
and
contactors
are
carefully
adjusted
at
the
facto
17
;
however
,
should
an
adjustment
of
these
devices
be
necessary
,
these
adjustments
are
explained
in
the
individual
instructions
for
each
device
.
After
all
connections
have
been
properly
made
,
all
parts
properly
assembled
,
and
all
components
thoroughly
inspected
and
adjusted
,
the
controller
is
ready
for
operation
.
Normal
Operation
1
.
After
all
power
and
control
connections
are
made
,
AND
WITH
THE
ISOLATING
DEVICE
OPEN
,
megger
between
phases
at
the
motor
terminals
,
and
between
each
phase
and
ground
stud
or
bus
,
to
ascertain
that
no
short
circuits
are
present
.
2
.
Close
the
compartment
doors
and
apply
power
to
the
controller
.
If
the
operating
handle
of
the
isolating
mechanism
cannot
be
moved
to
the
closed
position
,
it
may
be
that
the
mechanical
interlock
device
is
preventing
this
movement
.
To
move
the
handle
to
the
closed
position
,
the
highwoltage
door
must
be
fully
closed
and
the
contactor
must
be
open
.
Test
Power
Circuit
A
complete
operational
check
of
the
controller
can
be
made
without
applying
voltage
to
the
motor
or
to
the
bus
as
follows
:
1
.
The
isolating
-
device
handle
must
be
in
the
open
position
.
In
the
open
position
,
contacts
of
the
mechani
-
cally
operated
test
-
power
interlock
(
TPI
)
will
open
the
secondary
circuit
of
the
control
-
power
transformer
,
thereby
isolating
it
.
The
Test
-
Normal
Selector
Switch
(
TSW
)
must
be
in
the
Test
position
to
close
the
circuit
to
the
test
-
power
terminals
on
the
control
terminal
board
.
3
.
Close
the
isolating
-
device
handle
by
moving
the
handle
with
a
rapid
,
positive
motion
to
the
extreme
upper
position
until
it
latches
into
position
.
Unless
the
latch
(
pusher
)
snaps
out
when
the
handle
is
moved
to
2
.
Refer
to
the
elementary
and
connection
diagrams
for
the
extreme
positions
,
either
in
the
open
or
closed
the
required
control
voltage
,
frequency
,
and
test
-
power
terminal
designations
.
Connect
the
required
test
-
power
to
terminals
provided
on
the
terminal
board
in
the
low
-
voltage
control
compartment
.
Power
may
then
be
applied
to
the
low
-
voltage
control
circuit
and
the
circuit
tested
for
proper
operation
.
position
,
the
contact
marked
CPI
(
control
-
power
inter
-
lock
)
will
not
close
and
the
operation
is
not
complete
.
4
.
Operate
the
controller
in
the
normal
manner
with
the
pilot
devices
(
usually
,
push
buttons
)
provided
.
5
.
After
the
preliminary
operation
check
is
made
,
check
the
motor
for
proper
rotation
.
Preparation
of
Controller
for
Operation
Once
the
panel
is
in
place
and
the
cable
terminated
,
clean
the
inside
with
a
brush
,
soft
cloth
,
or
dry
compressed
air
.
Make
certain
that
any
dirt
,
dust
or
bits
of
packing
material
,
which
may
interfere
with
successful
operation
of
the
panel
devices
,
are
removed
from
the
panel
.
Caution
:
Care
should
be
taken
during
the
cleaning
operation
to
prevent
any
dirt
from
being
bloion
into
the
inaccessible
spaces
of
the
devices
.
Before
the
controller
can
be
operated
,
even
for
a
tryout
without
power
,
all
devices
must
be
placed
in
full
operating
condition
.
Also
,
check
to
ascertain
that
no
tools
or
loose
wires
have
been
left
within
the
panel
during
installation
.
Operate
each
device
by
hand
to
see
that
the
moving
parts
operate
freely
and
without
binding
.
Make
sure
that
all
electrical
contact
tips
are
clean
,
free
of
grease
and
dirt
,
and
Door
Opening
Procedure
General
To
open
the
high
-
voltage
doors
to
gain
access
to
the
contactor
or
motor
terminals
,
the
contactor
must
be
in
the
de
-
energized
position
.
If
the
contactor
is
energized
,
the
latch
on
the
disconnect
handle
cannot
be
pushed
in
,
the
handle
cannot
be
operated
,
nor
can
the
door
be
opened
.
Depressing
the
stop
button
de
-
energizes
the
contactor
.
The
latch
release
on
the
disconnect
handle
can
then
be
depressed
,
which
opens
an
electrical
interlock
in
the
secondary
of
the
control
-
power
transformer
.
When
the
latch
release
has
been
depressed
,
the
isolating
switch
handle
may
be
moved
to
the
lower
or
open
position
.
With
the
disconnect
handle
in
the
lower
position
,
the
high
-
voltage
door
may
be
opened
by
turning
the
V
\
turn
latches
.
27
Courtesy of NationalSwitchgear.com