GE Limitamp CR194 - Emergency Door-Defeater Latch Use; Inspection, Maintenance, and Servicing Guidelines; Vacuum Contactor Maintenance; Isolating Mechanism and Mechanical Interlock Adjustment

GE Limitamp CR194
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CR
194
Vacuum
Limitamp
400
Ampere
Control
Warning
:
All
power
must
be
removed
from
the
main
bus
before
attempting
to
adjust
the
isolating
switch
mechanism
.
1
.
After
removing
all
power
to
the
controller
,
and
as
described
in
steps
1
Sc
2
of
the
Mechanical
Operation
Check
,
rotate
the
isolating
switch
handle
to
the
ON
position
.
Then
remove
the
fixed
barrier
(
Figure
33
)
by
removing
the
retaining
screws
that
hold
it
in
place
.
Retain
the
hardware
for
reassembly
.
Some
of
the
barrier
mounting
hardware
is
nylon
type
hardware
.
Note
the
location
of
these
parts
so
they
may
be
reassembled
properly
.
2
.
Near
the
end
of
each
switch
blade
assembly
,
an
adjusting
nut
is
located
along
with
a
Belleville
washer
type
spring
.
To
adjust
the
blade
pressure
the
nut
must
be
adjusted
.
Loosen
the
small
set
screw
located
on
each
of
the
retaining
nuts
to
enable
adjustment
.
3
.
Loosen
the
adjusting
nut
at
the
top
of
the
blades
.
With
your
fingers
retighten
the
nut
until
all
the
slack
is
out
between
the
blades
,
stationary
contact
,
spring
washer
8
c
nut
,
then
tighten
an
additional
Vx
(
one
-
eighth
)
turn
.
This
procedure
provides
the
necessary
0.005
inch
spring
compression
of
the
blades
.
4
:
Tighten
the
set
screw
on
the
nut
to
lock
the
adjust
-
ment
in
position
.
Use
caution
to
prevent
turning
the
nut
on
the
main
screw
while
tightening
the
set
screw
.
5
.
When
the
adjustment
is
complete
for
all
three
phases
,
rotate
the
isolating
switch
handle
to
the
OFF
position
.
Then
,
apply
a
thin
coating
of
Mobil
Temp
SHC
-
32
grease
to
the
contact
surfaces
of
the
male
stab
portion
of
the
disconnect
.
To
properly
adjust
the
pivot
point
Belleville
washer
type
spring
,
return
the
isolating
switch
handle
to
the
ON
position
per
step
1
above
.
Then
,
follow
the
steps
below
:
1
.
On
each
phase
,
loosen
the
set
screw
on
the
pivot
point
adjusting
nut
.
2
.
Loosen
the
adjusting
nut
and
then
retighten
using
your
fingers
until
the
nut
is
just
snug
and
no
side
play
of
the
parts
is
evident
.
3
.
Using
wrenches
tighten
the
adjusting
nut
an
addi
-
tional
one
-
half
(
Vi
)
turn
and
tighten
the
set
screw
to
hold
the
adjustment
in
place
.
4
.
Rotate
the
isolating
switch
handle
to
the
OFF
position
,
then
reinstall
the
isolator
switch
barrier
.
If
necessary
the
viewing
window
may
be
cleaned
before
reinstallation
of
the
barrier
.
Use
a
soft
cloth
and
a
mild
soap
and
water
solution
or
a
commercial
cleaner
such
as
Windex
or
other
similar
cleaner
.
Warning
:
Severe
injury
or
death
may
result
if
the
equipment
is
energized
with
the
mechanical
interlocks
defeated
.
Remove
all
power
from
the
equipment
before
defeating
any
of
the
mechanical
interlocking
mechanisms
.
Door
-
Defeater
Latch
Warning
:
The
j
'
ollowing
steps
should
only
be
taken
as
a
last
resort
to
enter
a
malfunctioning
controller
;
It
is
imperative
that
all
power
to
the
main
bus
be
removed
before
proceeding
.
IN
CASE
OF
EMERGENCY
,
remove
all
power
to
the
controller
;
then
the
high
-
voltage
door
may
be
opened
with
the
contactor
in
the
closed
position
and
with
the
isolating
switch
closed
by
using
the
hex
-
head
bolts
,
located
to
the
lower
left
of
the
isolating
-
switch
handle
,
as
follows
:
Warning
:
Do
not
proceed
unless
all
power
to
the
controller
is
removed
.
Doors
must
not
be
opened
with
the
power
connected
to
the
bus
.
1
.
Turn
the
door
latches
Z
\
turn
counterclockwise
.
2
.
'
Remove
the
right
-
hand
hex
-
head
bolt
,
as
shown
in
Figure
52
.
3
.
Turn
the
left
-
hand
bolt
]
A
turn
counterclockwise
.
Figure
53
shows
the
bolts
from
the
inside
.
The
door
may
then
be
opened
.
Warning
:
Defeating
the
door
interlock
leaves
the
controller
connected
to
the
bus
.
The
bus
power
must
be
removed
.
On
some
one
-
high
enclosures
,
the
low
-
voltage
control
panel
serves
as
a
barrier
to
isolate
the
high
-
vokage
control
-
power
transformer
and
fuses
.
An
interference
pin
,
shown
in
Figure
54
,
prevents
swinging
this
low
-
voltage
panel
out
until
the
high
-
voltage
door
is
opened
.
Inspection
,
Maintenance
,
and
Servicing
Vacuum
Contactor
Complete
maintenance
and
adjustment
instructions
for
the
high
-
voltage
contactors
are
presented
in
GEH
-
5306
.
Refer
to
that
instruction
for
all
problems
of
servicing
and
adjust
-
ing
;
and
to
the
proper
renewal
parts
bulletin
for
renewal
parts
.
Contactor
tip
life
depends
on
the
severity
of
the
service
,
but
in
any
case
,
it
is
recommended
that
the
contactor
tip
wear
be
checked
at
least
once
a
year
or
in
very
high
duty
cycle
operations
,
after
every
250
,
000
operations
.
Isolating
Mechanism
and
Mechanical
Interlock
Warning
:
Under
no
circumstances
should
the
isolation
switch
be
inspected
or
adjusted
with
power
applied
to
the
main
bus
.
The
quick
-
make
quick
-
break
isolation
switch
assembly
is
adjusted
and
tested
at
the
factory
.
Under
normal
circumstances
the
switch
does
not
need
adjustment
,
however
,
if
conditions
require
it
the
switch
may
be
adjusted
in
the
field
.
To
adjust
the
isolating
switch
the
following
steps
should
be
followed
:
29
Courtesy of NationalSwitchgear.com