CHAPTER 4: SETPOINTS PROTECTION
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–199
Figure 4-66: Neutral Directional Overcurrent Protection logic diagram
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
SETTING
SETTING
SETTING
SETTING
SETTINGS
SETTING
SETTING
NEUTRAL DIR OC
FUNCTION:
NEUTRAL DIR OC POL
VOLT:
NEUTRAL DIR OC
POLARIZING:
BLOCK:
NEUTRAL DIR OC FWD
LIMIT ANGLE:
NEUTRAL DIR OC FWD
ECA:
NEUTRAL DIR OC REV
LIMIT ANGLE:
NEUTRAL DIR OC FWD
PICKUP:
NEUTRAL DIR OC REV
PICKUP:
NEUTRAL DIR OC
POS-SEQ RESTRAINT
Ntrl Dir OC FWD
Ntrl Dir OC REV
Disabled=0
Measured VX
Voltage
Calculated V_0
}
}
Current
Ground Crt (IG)
Zero Seq Crt (I_0)
Dual
NOTE:
1) CURRENT POLARIZING IS POSSIBLE ONLY IN RELAYS WITH
THE GROUND CURRENT INPUTS CONNECTED TO
AN ADEQUATE CURRENT POLARIZING SOURCE
2) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN
I_1 IS BELOW 0.8 x CT
Off=0
Enabled=1
AND
AND
AND
AND
AND
AND
AND
OR
OR
OR
OR
IG 0.05xCT
3( I_0 - K I_1) PICKUP
3(I_0 - K I_1 ) PICKUP
Voltage Polarization
Current Polarization
-3V_0
3I_0
FWD
FWD
FWD
REV
REV
REV
RUN
RUN
RUN
RUN
1.25 cy
1.5 cy
NEUTRAL DIR OC POS-
SEQ RESTRAINT:
892716A1.cdr
TO NEUTRAL TOC AND
IOC ELEMENTS
TO NEUTRAL TOC AND
IOC ELEMENTS
AND