Appendix B -Settings and Signals
P446SV
B160
P446SV-TM-EN-1
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
cross polarization to allow testing with test sets that can not simulate a real fault
291
Test Loopback
DDB_LOOPBACK_TEST
Loopback test in service (external or internal)
292
Test IM64
DDB_IM64_TEST_MODE
Indication that relay is in test mode
293
VT Fail Alarm
DDB_VTS_INDICATION
VTS indication alarm- failed VT (fuse blow) detected by VT supervision
294
CT1 Fail Alarm
DDB_CTS_INDICATION
CT1S indication alarm (CT supervision alarm)
In the cases of two CTs:
- If standard CTS is used, this indication is ON in case of failure on any of the CTs
- If Diff CTS is used this indication is ON in case of failure on CT1
295
CT2 Fail Alarm
DDB_CT2S_INDICATION
CT2S indication alarm (CT supervision alarm).
This indication is ON If Diff CTS is used and there is a failure on CT2
297
Power Swing
DDB_PSB_ALARM
Powerswing blocking will block any distance zone selected in the setting file
298
CB1 Fail Alarm
DDB_BREAKER_FAIL_ALARM
Circuit breaker (CB1) fail alarm
299
CB1 Monitor Alm
DDB_CB_MONITOR_ALARM
CB1 Monitor Alarm
300
CB1 Mon LO Alarm
DDB_CB_MONITOR_LOCKOUT
CB1 Monitor Lockout Alarm
301
CB1 Status Alm
DDB_CB_STATUS_ALARM
CB1 Status Alarm - set when CB1 status is determined by inputs from BOTH 52A and 52B type auxiliary contacts (setting "CB1 Status
Input = 52A&52B-xPole), and both inputs are in the same state (both = 0 or both = 1) for time period => 5sec, indicating a problem with
the auxiliary switch mechanism).
302
CB1 Trip Fail
DDB_CB_FAILED_TO_TRIP
CB1 Failed to Trip - alarm set if CB1 does not trip within set Trip Pulse Time when CB1 trip command is issued.
303
CB1 Close Fail
DDB_CB_FAILED_TO_CLOSE
CB1 Failed to Close - alarm set if CB1 fails to close within set Close Pulse Time when CB1 close command is issued
304
ManCB1 Unhealthy
DDB_CONTROL_CB_UNHEALTHY
Control CB1 Unhealthy - alarm set if CB1 remains "unhealthy" for CB Control set time "CB Healthy Time" when operator controlled CB1
close sequence is initiated. (Please see description for CB Control setting "CB Healthy Time").
305
NoCS CB1ManClose
DDB_CONTROL_NO_CHECK_SYNC
Control No Checksync - alarm set if selected system check conditions for manual closing CB1 remain unsatisfied for CB Control set
time "Check Sync Time" when operator controlled CB1 close sequence is initiated. (Please see description for CB Control setting
"Check Sync Time").
306
CB1 AR Lockout
DDB_AR_LOCKOUT
Autoclose Lockout/RLY BAR - alarm set when CB1 autoreclose is locked out.
307
AR CB1 Unhealthy
DDB_AR_CB_UNHEALTHY
No Healthy (AR) - alarm set if CB1 remains "unhealthy" for Autoreclose set time "CB Healthy Time" when CB1 close sequence is
initiated by autoreclose function. (Please see description for Autoreclose setting "CB Healthy Time").
308
AR CB1 No C/S
DDB_AR_NO_CHECK_SYNC
No Check Sync / AR Fail - alarm set if selected system check conditions for autoreclosing CB1 remain unsatisfied for Autoreclose set
time "Check Sync Time" when CB1 close sequence is initiated by autoreclose function. (Please see description for Autoreclose setting
"Check Sync Time").
311
Signalling Fail
DDB_SIGNALLING_FAILURE
If a differential protection communication path has remained failed for a period which is longer than the “Comms Fail Timer”, this
alarm is ON
314
IM64 SchemeFail
DDB_FIB_IM_SCHEME_FAIL
It indicates that communications between relays are completely lost and therefore IM64 does not work
315
IEEE C37.94 Fail
DDB_IEEE_37_94
t will appear in case of at least one of the following: CH1 (or CH2) loss of signal, CH1 (or CH2) PATH_YELLOW or CH1 (or CH2) BAD_RX_N
317
Aid 1 Chan Fail
DDB_AIDED1_LGS_ALARM
Aided channel scheme 1 - channel out of service indication, indicating channel failure
318
Aid 2 Chan Fail
DDB_AIDED2_LGS_ALARM
Aided channel scheme 2 - channel out of service indication, indicating channel failure
319
F out of Range
DDB_FREQ_ALARM