P446SV
Appendix B -Settings and Signals
P446SV-TM-EN-1
B161
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
Frequency out of range alarm
320
CB2 Fail Alarm
DDB_BREAKER_FAIL_ALARM_2
Circuit breaker 2 fail alarm
321
CB2 Monitor Alm
DDB_CB2_MONITOR_ALARM
This alarm indicates that DDB CB2 I ^ Maint. Alarm (1113) or DDB CB2 OPs Maint. (1115) or DDB CB2 Time Maint. (1117)
322
CB2 Mon LO Alarm
DDB_CB2_MONITOR_LOCKOUT
This alarm indicates that DDB CB2 I ^ Lockout Alarm (1114) or DDB CB Ops Lock (1116) or DDB CB Time lockout (1118)
323
CB2 Status Alm
DDB_CB2_STATUS_ALARM
Indication of problems by circuit breaker 2 state monitoring - example defective auxiliary contacts
324
CB2 Trip Fail
DDB_CB2_FAILED_TO_TRIP
Circuit breaker 2 failed to trip (after a manual/operator) trip command
325
CB2 Close Fail
DDB_CB2_FAILED_TO_CLOSE
Circuit breaker 2 failed to close (after a manual/operator or auto-reclose close command)
326
ManCB2 Unhealthy
DDB_CONTROL_CB2_UNHEALTHY
Manual circuit breaker unhealthy output signal indicating that the circuit breaker 2 has not closed successfully after a manual close
command. (A successful close also requires The circuit breaker healthy signal to reappear within the "healthy window" timeout)
327
NoCS CB2ManClose
DDB_CONTROL_NO_CHECK_SYNC_2
Indicates that the check synchronism signal has failed to appear for a manual close
328
CB2 AR Lockout
DDB_AR_LOCKOUT_2
Indicates an auto-reclose lockout condition - no further auto-reclosures possible until resetting
329
AR CB2 Unhealthy
DDB_AR_CB2_UNHEALTHY
Auto-reclose circuit breaker unhealthy signal, output from auto-reclose logic. Indicates during auto-reclose in progress, if the circuit
breaker has to become healthy within the circuit breaker healthy time window
330
AR CB2 No C/S
DDB_AR_NO_CHECK_SYNC_2
Indicates during auto-reclose in progress, if system checks have not been satisfied within the check synchronizing time window
331
Invalid AR Mode
DDB_INVALID_AR_MODE
AR Mode selected via optos is not supported
333
InValid Mesg Fmt
DDB_MESSAGE_FORMAT_FAIL
Invalid Message Format
334
Main Prot. Fail
DDB_MAIN_PROTECTION_FAIL
Indicates a failure in differential or distance or DEF
337
Comms Changed
DDB_PROT_COMMS_MODE
This is an alarm which indicates that C3794 comms have been changed to standard or vice versa and relay must be rebooted
338
Max Prop. Alarm
DDB_MAX_PROP_DELAY_ALARM
Maximum Propagation Delay Alarm
339
Prot'n Disabled
DDB_PROTECTION_DISABLED
Protection disabled
340
9-2 Sample Alarm
DDB_ALARM_9_2_SAV
Means the abnormal state of IEC 61850-9-2LE sample
342
9-2LE Cfg Alarm
DDB_9_2_SAV_CFG_ALARM
This DDB means the IEC 61850-9-2LE configure is wrong
344
SR User Alarm 1
DDB_ALARM_56
Triggers user alarm 1 message to be alarmed on LCD display (self-resetting)
345
SR User Alarm 2
DDB_ALARM_57
Triggers user alarm 2 message to be alarmed on LCD display (self-resetting)
346
SR User Alarm 3
DDB_ALARM_58
Triggers user alarm 3 message to be alarmed on LCD display (self-resetting)
347
SR User Alarm 4
DDB_ALARM_59
Triggers user alarm 4 message to be alarmed on LCD display (self-resetting)
348
MR User Alarm 5
DDB_ALARM_60
Triggers user alarm 5 message to be alarmed on LCD display (manual-resetting)
349
MR User Alarm 6
DDB_ALARM_61
Triggers user alarm 6 message to be alarmed on LCD display (manual-resetting)
350
MR User Alarm 7
DDB_ALARM_62
Triggers user alarm 7 message to be alarmed on LCD display (manual-resetting)
351
MR User Alarm 8
DDB_ALARM_63
Triggers user alarm 8 message to be alarmed on LCD display (manual-resetting)
352
Battery Fail
DDB_BATTERY_FAIL