EasyManua.ls Logo

GE MiCOM P40 - Page 908

GE MiCOM P40
962 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B -Settings and Signals
P446SV
B162
P446SV-TM-EN-1
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
Front panel miniature battery failure - either battery removed from slot, or low voltage
353
Field Volts Fail
DDB_FIELD_VOLTS_FAIL
48V field voltage failure
354
Rear Comm 2 Fail
DDB_REAR_COMMS_FAIL
Comm2 hardware failure - second rear communications board
355
GOOSE IED Absent
DDB_GOOSE_MISSING_IED
The IED is not subscribed to a publishing IED in the current scheme
356
NIC Not Fitted
DDB_ECARD_NOT_FITTED
Ethernet board not fitted
357
NIC No Response
DDB_NIC_NOT_RESPONDING
Ethernet board not responding
358
NIC Fatal Error
DDB_NIC_FATAL_ERROR
Ethernet board unrecoverable error
359
NIC Soft. Reload
DDB_NIC_SOFTWARE_RELOAD
Ethernet problem
360
Bad TCP/IP Cfg.
DDB_INVALID_NIC_TCPIP_CONFIG
Ethernet problem
361
Bad OSI Config.
DDB_INVALID_NIC_OSI_CONFIG
Ethernet problem
362
NIC Link Fail
DDB_NIC_LINK_FAIL
Ethernet link lost
363
NIC SW Mis-Match
DDB_SW_MISMATCH_ALARM
Ethernet board software not compatible with main CPU
364
IP Addr Conflict
DDB_NIC_IP_ADDRESS_CONFLICT
The IP address of the IED is already used by another IED
365
IM Loopback
DDB_INTERMICOM_LOOPBACK
EIA(RS)232 InterMiCOM indication that Loopback testing is in progress
366
IM Message Fail
DDB_INTERMICOM_MESSAGE
EIA(RS)232 InterMiCOM Message Failure alarm. Setting that is used to alarm for poor channel quality. If during the fixed 1.6 s rolling
window the ratio of invalid messages to the total number of messages that should be received (based upon the ‘Baud Rate’ setting)
exceeds the above threshold, a ‘Message Fail’ alarm will be issued
367
IM Data CD Fail
DDB_INTERMICOM_DCD
EIA(RS)232 InterMiCOM Data Channel Detect Fail i.e. modem failure
368
IM Channel Fail
DDB_INTERMICOM_CHANNEL
EIA(RS)232 InterMiCOM Channel Failure alarm. No messages were received during the alarm time setting
369
Backup Setting
DDB_BACKUP_DATA_IN_USE
This is an alarm that is ON if any setting fail during the setting changing process. If this happens, the relay will use the last known
good setting
370
Reserved
DDB_PLATFORM_ALARM_19
Platform Alarm 19
371
Reserved
DDB_PLATFORM_ALARM_20
Platform Alarm 20
372
SNTP Failure
DDB_SNTP_FAIL_ALARM
SNTP synchronisation fail alarm
373
NIC MemAllocFail
DDB_NIC_MEM_ALLOC_FAIL_ALARM
MMS library memory allocation failure
374
PTP Failure
DDB_PTP_FAIL_ALARM
IEEE 1588 PTP time synchronisation failure alarm
375
Reserved
DDB_PLATFORM_ALARM_24
Platform Alarm 24
376
Reserved
DDB_PLATFORM_ALARM_25
Platform Alarm 25
377
BBRAM Failure
DDB_BBRAM_VERIFY_FAIL
BBRAM Verify Fail
378
Reserved
DDB_PLATFORM_ALARM_27
Platform Alarm 27
379
Reserved
DDB_PLATFORM_ALARM_28
Platform Alarm 28