Appendix B -Settings and Signals
P446SV
B164
P446SV-TM-EN-1
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
409
ISEF>1 Timer Blk
DDB_SEF_1_TIMER_BLOCK
Block sensitive earth fault stage 1 time delayed trip
410
ISEF>2 Timer Blk
DDB_SEF_2_TIMER_BLOCK
Block sensitive earth fault stage 2 time delayed trip
411
ISEF>3 Timer Blk
DDB_SEF_3_TIMER_BLOCK
Block sensitive earth fault stage 3 time delayed trip
412
ISEF>4 Timer Blk
DDB_SEF_4_TIMER_BLOCK
Block sensitive earth fault stage 4 time delayed trip
414
V<1 Timer Block
DDB_PUV_1_TIMER_BLOCK
Block phase undervoltage stage 1 time delayed trip
415
V<2 Timer Block
DDB_PUV_2_TIMER_BLOCK
Block phase undervoltage stage 2 time delayed trip
416
V>1 Timer Block
DDB_POV_1_TIMER_BLOCK
Block phase overvoltage stage 1 time delayed trip
417
V>2 Timer Block
DDB_POV_2_TIMER_BLOCK
Block phase overvoltage stage 2 time delayed trip
418
VN>1 Timer Blk
DDB_RESOV_1_TIMER_BLOCK
Block residual overvoltage stage 1 time delayed trip
419
VN>2 Timer Blk
DDB_RESOV_2_TIMER_BLOCK
Block residual overvoltage stage 2 time delayed trip
420
CB1Aux 3ph(52-A)
DDB_CB_THREE_PHASE_52A
52-A (CB1 closed) CB auxiliary input (3 phase)
421
CB1Aux A (52-A)
DDB_CB_PHASE_A_52A
52-A (CB1 A phase closed) CB auxiliary
422
CB1Aux B (52-A)
DDB_CB_PHASE_B_52A
52-A (CB1 B phase closed) CB auxiliary
423
CB1Aux C (52-A)
DDB_CB_PHASE_C_52A
52-A (CB1 C phase closed) CB auxiliary
424
CB1Aux 3ph(52-B)
DDB_CB_THREE_PHASE_52B
52-B CB Contact Input
425
CB1Aux A (52-B)
DDB_CB_PHASE_A_52B
52-B CB Contact Input A Phase
426
CB1Aux B (52-B)
DDB_CB_PHASE_B_52B
52-B CB Contact Input B Phase
427
CB1Aux C (52-B)
DDB_CB_PHASE_C_52B
52-B CB Contact Input C Phase
428
CB2 Aux3ph(52-A)
DDB_CB2_THREE_PHASE_52A
52-A (CB2 closed) CB2 auxiliary input (3 phase)
429
CB2 Aux A(52-A)
DDB_CB2_PHASE_A_52A
52-A (CB2 A phase closed) CB auxiliary
430
CB2 Aux B(52-A)
DDB_CB2_PHASE_B_52A
52-A (CB2 B phase closed) CB2 auxiliary
431
CB2 Aux C(52-A)
DDB_CB2_PHASE_C_52A
52-A (CB2 C phase closed)CB2 auxiliary
432
CB2 Aux3ph(52-B)
DDB_CB2_THREE_PHASE_52B
52-B (CB2 open) CB2 auxiliary input (3 phase)
433
CB2 Aux A(52-B)
DDB_CB2_PHASE_A_52B
52-B (CB2 A phase open) CB2 auxiliary input
434
CB2 Aux B(52-B)
DDB_CB2_PHASE_B_52B
52-B (CB2 B phase open) CB2 auxiliary input
435
CB2 Aux C(52-B)
DDB_CB2_PHASE_C_52B
52-B (CB2 C phase open) CB2 auxiliary input
436
CB1 Healthy
DDB_CB_HEALTHY
Circuit breaker healthy (input to auto-recloser - that the CB1 has enough energy to allow re-closing)
437
CB2 Healthy
DDB_CB2_HEALTHY
Circuit breaker healthy (input to auto-recloser - that the CB2 has enough energy to allow re-closing)
438
MCB/VTS
DDB_VTS_MCB_OPTO
VT supervision input - signal from external miniature circuit breaker showing MCB tripped