P446SV
Appendix B -Settings and Signals
P446SV-TM-EN-1
B165
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
439
Init Trip CB1
DDB_LOGIC_INPUT_TRIP
Initiate tripping of circuit breaker 1 from a manual command
440
Init Close CB1
DDB_LOGIC_INPUT_CLOSE
Initiate closing of circuit breaker 1 from a manual command
441
Init Trip CB2
DDB_LOGIC_INPUT_TRIP_2
Initiate tripping of circuit breaker 2 from a manual command
442
Init Close CB2
DDB_LOGIC_INPUT_CLOSE_2
Initiate closing of circuit breaker 2 from a manual command
443
Rst CB1 CloseDly
DDB_RESET_CB_CLOSE_DELAY
Reset Manual CB Close Timer Delay (stop & reset Manual Close Delay time for closing CB1).
444
Reset Relays/LED
DDB_RESET_RELAYS_LEDS
Reset latched relays & LEDs (manual reset of any lockout trip contacts, auto-reclose lockout, and LEDs)
445
Reset Thermal
DDB_RESET_THERMAL
Reset thermal state to 0%
446
Rst CB1 Lockout
DDB_RESET_LOCKOUT
Reset Lockout Opto Input to reset CB1 Lockout state
447
Rst CB1 Data
DDB_RESET_ALL_VALUES
Reset CB1 Maintenance values
448
Block CB1 AR
DDB_BLOCK_AR
DDB mapped in PSL from opto or comms input. External signal to force CB1 autoreclose to lockout.
451
Pole Discrep.CB1
DDB_INP_TR2P
Pole discrepancy (from external detector) - input used to force a 2nd single pole trip to move to a 3 pole auto-reclose cycle
452
Loopback Mode
DDB_INTERNAL_LOOPBACK
To enable loopback mode via opto input
458
Inhibit WI
DDB_INHIBIT_WI
Inhibit weak infeed aided scheme logic
459
Test Mode
DDB_TEST_MODE
Commissioning tests - automatically places relay in test mode
460
103 CommandBlock
DDB_COMMAND_BLOCKING
For IEC-870-5-103 protocol only, used for "Command Blocking" (relay ignores SCADA commands)
461
103 MonitorBlock
DDB_MONITOR_BLOCKING
For IEC-870-5-103 protocol only, used for "Monitor Blocking" (relay is quiet - issues no messages via SCADA port)
463
Inhibit I>1
DDB_INHIBIT_POC1
Inhibit stage 1 overcurrent protection
464
Inhibit I>2
DDB_INHIBIT_POC2
Inhibit stage 2 overcurrent protection
465
Inhibit I>3
DDB_INHIBIT_POC3
Inhibit stage 3 overcurrent protection
466
Inhibit I>4
DDB_INHIBIT_POC4
Inhibit stage 4 overcurrent protection
467
Inhibit IN>1
DDB_INHIBIT_EF1
Inhibit stage 1 earth fault protection
468
Inhibit IN>2
DDB_INHIBIT_EF2
Inhibit stage 2 earth fault protection
469
Inhibit IN>3
DDB_INHIBIT_EF3
Inhibit stage 3 earth fault protection
470
Inhibit IN>4
DDB_INHIBIT_EF4
Inhibit stage 4 earth fault protection
471
Inhibit V<1
DDB_INHIBIT_UV1
Inhibit stage 1 undervoltage protection
472
Inhibit V<2
DDB_INHIBIT_UV2
Inhibit stage 2 undervoltage protection
473
Inhibit V>1
DDB_INHIBIT_OV1
Inhibit stage 1 overvoltage protection
474
Inhibit V>2
DDB_INHIBIT_OV2
Inhibit stage 2 overvoltage protection
475
Inhibit VN>1
DDB_INHIBIT_RESOV1
Inhibit stage 2 overvoltage protection