A-4 F650 Digital Bay Controller GE Multilin
A.1 LOGIC OPERANDS APPENDIX A
A
Contact Output Status Board J (8 elements) - CIO
MODULE
CONT OP_J_01 Contact output 1 Board J operation
CONT OP_J_02 Contact output 2 Board J operation
... ...
CONT OP_J_08 Contact output 8 Board J operation
Board J Status - CIO MODULE BOARD J STATUS
Board J status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board
Switchgear status (16 elements)
SWITCH 1 A INPUT Contact input type A to switchgear Function 1
SWITCH 1 B INPUT Contact input type B to switchgear Function 1
SWITCH 2 A INPUT Contact input type A to switchgear Function 2
SWITCH 2 B INPUT Contact input type B to switchgear Function 2
... ...
SWITCH 16 A INPUT Contact input type A to switchgear Function 16
SWITCH 16 B INPUT Contact input type B to switchgear Function 16
Switchgear outputs (16 elements)
SWITCH 1 A STATUS Contact logic output type A from switchgear Function 1
SWITCH 1 B STATUS Contact logic output type B from switchgear Function 1
SWITCH 2 A STATUS Contact logic output type A from switchgear Function 2
SWITCH 2 B STATUS Contact logic output type B from switchgear Function 2
... ...
SWITCH 16 A STATUS Contact logic output type A from switchgear Function 16
SWITCH 16 B STATUS Contact logic output type B from switchgear Function 16
Switchgear states (16 elements)
SWITCH 1 OPEN switchgear 1 open
SWITCH 1 CLOSED switchgear 1 closed
SWITCH 1 00_ERROR Error 00 switchgear 1 (contact A = 0, contact B = 0)
SWITCH 1 11_ERROR Error 11 switchgear 1 (contact A = 1, contact B = 1)
SWITCH 2 OPEN switchgear 2 open
SWITCH 2 CLOSED switchgear 2 closed
SWITCH 2 00_ERROR Error 00 switchgear 2 (contact A = 0, contact B = 0)
SWITCH 2 11_ERROR Error 11 switchgear 2 (contact A = 1, contact B = 1)
... ...
SWITCH 16 OPEN switchgear 16 open
SWITCH 16 CLOSED switchgear 16 closed
SWITCH 16 00_ERROR Error 00 switchgear 16 (contact A = 0, contact B = 0)
SWITCH 16 11_ERROR Error 11 switchgear 16 (contact A = 1, contact B = 1)