Appendix B - Settings and Signals
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
To enable (activate) or disable (turn off) the back up Earth Fault Protection function. IN >stages: ANSI 50N/51N/67N
Earth Fault 09 13 Enabled
Enabled
To enable (activate) or disable (turn off) the back up Earth Fault Protection function. IN >stages: ANSI 50N/51N/67N
SEF/REF Prot'n 09 15 Disabled
Enabled
To enable (activate) or disable (turn off) the Sensitive Earth Fault/Restricted Earth fault Protection function.
ISEF >stages: ANSI 50N/51N/67N. IREF>stage: ANSI 64.
Residual O/V NVD 09 16 Disabled
Enabled
To enable (activate) or disable (turn off) the Residual Overvoltage Protection function. VN>stages: ANSI 59N
Thermal Overload 09 17 Disabled
Enabled
To enable (activate) or disable (turn off) the Thermal Overload Protection function. ANSI 49.
Volt Protection 09 1D Disabled
Enabled
To enable (activate) or disable (turn off) the Voltage Protection (under/overvoltage/remote) function. V<, V>, Cp V> stages: ANSI 27/59/59R.
Freq Protection 09 1E Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Frequency Protection (under/over frequency) function. F<, F> stages: ANSI 81.
df/dt Protection 09 1F Disabled
Enabled
To enable (activate) or disable (turn off) the Rate of change of Frequency Protection function. df/dt> stages: ANSI 81.
CB Fail 09 20 Disabled
Enabled
To enable (activate) or disable (turn off) the Circuit Breaker Fail Protection function: ANSI 50BF.
Supervision 09 21 Enabled
Enabled
To enable (activate) or disable (turn off) the Supervision (VTS & CTS) functions: ANSI 47/27/46.
System Checks 09 23 Disabled
Enabled
To enable (activate) or disable (turn off) the System Checks (Check Sync. and Voltage Monitor) function: ANSI 25.
Auto-Reclose 09 24 Disabled
Enabled
To enable (activate) or disable (turn off) the Auto-reclose function. ANSI 79.
Input Labels 09 25 Visible
Visible
Sets the Input Labels menu visible further on in the IED settings menu.
Output Labels 09 26 Visible
Visible
Sets the Output Labels menu visible further on in the IED settings menu.
CT & VT Ratios 09 28 Visible
Visible
Sets the Current & Voltage Transformer Ratios menu visible further on in the IED settings menu.