Appendix B - Settings and Signals
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Ethernet versions only. To enable (activate) or disable (turn off) Read Only Mode of Network Interface Card.
LCD Contrast 09 FF 11
From 0 to 31 in steps of 1
[Indexed String]
This column contains settings for Current and Voltage Transformer ratios
Main VT Primary 0A 01 110
From 100 to 1000000 in steps of 1
[Courier Number (voltage)]
Sets the main voltage transformer input primary voltage.
Main VT Sec'y 0A 02 110
From 80*V1 to 140*V1 in steps of 1*V1
[Courier Number (voltage)]
Sets the main voltage transformer input secondary voltage.
CS VT Primary 0A 03 110
From 100 to 1000000 in steps of 1
[Courier Number (voltage)]
Sets the System Check Synchronism voltage transformer input primary voltage.
CS VT Secondary 0A 04 110
From 80*V2 to 140*V2 in steps of 1*V2
[Courier Number (voltage)]
Sets the System Check Synchronism voltage transformer input secondary voltage.
Phase CT Primary 0A 07 1
From 1 to 30000 in steps of 1
[Courier Number (current)]
Sets the phase current transformer input primary current rating.
Phase CT Sec'y 0A 08 1
[Courier Number (current)]
Sets the phase current transformer input secondary current rating.
SEF CT Primary 0A 0B 1
From 1 to 30000 in steps of 1
[Courier Number (current)]
Sets the sensitive earth fault current transformer input primary current rating.
SEF CT Secondary 0A 0C 1
1 or 5
[Courier Number (current)]
Sets the sensitive earth fault current transformer input secondary current rating.
MComp CT Primary 0A 0D 1
From 1 to 30000 in steps of 1
[Courier Number (current)]
Sets the mutual compensation current transformer input primary current rating.
MComp CT Sec'y 0A 0E 1
1 or 5
[Courier Number (current)]
Sets the mutual compensation current transformer input secondary current rating.
CS Input 0A 0F AN
BN
CN
AB
BC
CA
AN / 1.732
BN / 1.732
CN / 1.732
Selects the System Check Synchronism Input voltage measurement.
Main VT Location 0A 10 Line
Bus
[Indexed String]
Selects the main voltage transformer location.
CT Polarity 0A 11 Standard
Inverted
To invert polarity (180 °) of the CT
SEF CT Polarity 0A 13 Standard
Inverted