EasyManua.ls Logo

GE POWER/VAC 13.8 - Switchgear Installation Procedures; Location Requirements; Anchoring Methods; Indoor Equipment Floor Preparation

GE POWER/VAC 13.8
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION
Before
any
installation
work
is
done
,
consult
and
study
all
A
drawings
furnished
by
the
General
Electric
Company
for
the
^
particular
requisition
.
These
drawings
include
arrangement
and
floor
plan
drawings
,
elementary
,
connection
and
inter
-
connection
diagrams
and
a
device
summary
.
will
not
be
level
with
respect
to
the
stationary
element
.
The
switchgear
structure
can
be
secured
by
bolting
it
to
the
floor
channels
using
at
least
5
/
8
inch
bolts
at
locations
shown
in
Fig
.
5
.
Plug
welding
can
also
be
used
at
the
same
locations
if
desired
.
Occasionally
additional
shipping
members
are
installed
in
the
primary
area
to
protect
against
shipping
damage
.
CAUTION
Shipping
braces
must
be
removed
prior
to
energizing
.
Shipping
braces
are
marked
with
yellow
labels
.
Shipping
braces
may
be
applied
to
devices
as
well
as
to
current
-
carrying
conductors
.
After
the
shipping
braces
have
been
removed
,
all
joints
must
be
properly
tightened
and
insulated
before
energizing
the
bus
.
Mats
,
screens
,
railings
,
etc
.
which
an
>
external
to
the
switchgear
,
but
which
may
be
required
to
meet
any
local
codes
,
must
be
furnished
by
the
purchaser
.
Provision
should
be
made
in
the
floor
for
conduits
for
primary
and
secondary
cables
,
located
as
shown
on
the
floor
plan
drawing
furnished
for
the
particular
requisition
.
If
desired
,
the
conduits
may
be
installed
before
the
switchgear
.
Consideration
should
be
given
to
conduits
which
might
be
required
for
future
connections
.
Conduits
must
extend
no
more
than
one
inch
above
the
finished
floor
prior
to
the
installation
of
the
switchgear
.
If
shipped
in
more
than
one
section
,
shipping
sections
must
be
assembled
in
the
proper
sequence
due
to
the
location
of
conduits
.
The
left
-
hand
sec
-
tion
of
a
switchgear
line
-
up
must
be
positioned
in
its
final
location
first
.
Then
the
section
located
immediately
to
the
right
must
be
positioned
as
close
as
the
lifting
members
permit
with
the
front
in
alignment
with
the
first
section
.
Remove
the
lifting
members
and
then
push
or
jack
the
unit
to
the
left
until
it
is
flush
with
the
first
section
.
Be
sure
to
distribute
the
forces
over
the
side
frame
using
appropriate
timbers
so
as
not
to
deform
or
damage
the
surface
of
the
structure
.
LOCATION
The
recommended
aisle
space
required
at
the
front
and
at
the
rear
of
the
equipment
is
shown
on
the
floor
plan
drawing
furnished
for
the
particular
requisition
.
The
space
at
the
front
must
be
sufficient
to
permit
the
insertion
and
with
-
drawal
of
the
circuit
breakers
,
and
their
transfer
to
other
units
.
No
part
of
a
foundation
PAD
or
SILL
may
extend
more
than
3
inches
beyond
the
front
of
the
equip
-
ment
.
OUTDOOR
EQUIPMENT
Switchgear
support
should
be
concrete
or
reinforced
con
-
crete
with
depth
,
fill
,
drainage
,
etc
.
,
according
to
recom
-
mended
foundation
design
for
the
loading
,
type
of
con
-
struction
,
and
local
conditions
involved
.
The
base
furnished
with
the
switchgear
should
be
supported
on
a
level
surface
over
the
full
area
of
the
switchgear
.
Steel
supporting
mem
-
bers
should
be
furnished
if
required
for
leveling
the
founda
-
tion
and
supporting
the
switchgear
.
Refer
to
Fig
.
6
for
recommended
foundation
and
anchoring
.
Primary
and
secondary
conduits
should
be
installed
in
accordance
with
the
requisition
drawings
,
before
the
equip
-
ment
is
put
into
place
.
Conduits
must
extend
no
more
than
one
inch
above
the
finished
floor
prior
to
the
installation
of
the
switchgear
.
»
The
space
at
the
rear
must
be
sufficient
for
installation
of
cables
,
and
for
inspection
and
maintenance
.
ANCHORING
INDOOR
EQUIPMENT
FLOOR
PREPARATION
The
station
floor
must
be
strong
enough
to
prevent
sag
-
ging
due
to
weight
of
the
switchgear
structure
and
to
with
-
stand
the
impact
stress
caused
by
the
opening
of
the
circuit
breakers
under
short
circuit
conditions
.
The
impact
loading
is
approximately
llA
times
the
static
load
.
Suitable
means
must
be
provided
by
the
purchaser
for
anchoring
the
equipment
to
the
floor
.
It
is
essential
that
the
floor
be
level
to
avoid
distortion
of
the
switchgear
structure
and
that
the
equipment
be
completely
aligned
prior
to
final
anchoring
.
The
recommended
floor
construction
is
shown
in
Fig
.
5
.
The
floor
channels
must
be
level
and
straight
with
respect
to
each
other
.
Steel
shims
should
be
used
for
final
leveling
of
the
switchgear
,
if
necessary
.
Care
should
be
taken
to
provide
a
smooth
,
hard
,
and
level
floor
under
and
in
front
of
the
units
to
facilitate
installation
and
removal
of
the
breaker
.
If
the
floor
is
not
level
and
flush
with
the
floor
channels
,
it
will
be
difficult
to
handle
the
breaker
because
it
When
outdoor
pieces
of
equipment
are
shipped
in
more
than
one
section
,
the
roof
joint
between
the
sections
must
be
assembled
as
shown
in
Fig
.
7
.
Shipping
sections
must
be
assembled
in
the
proper
sequence
due
to
the
location
of
con
-
duits
.
The
left
-
hand
section
of
a
switchgear
line
-
up
must
be
positioned
in
its
final
location
first
.
Then
the
section
located
immediately
to
the
right
must
be
positioned
as
close
as
the
lifting
members
permit
with
the
front
in
alignment
with
the
first
section
.
Remove
the
lifting
members
and
then
push
or
jack
the
unit
to
the
left
until
it
is
flush
with
the
first
section
.
Be
sure
to
distribute
the
forces
over
the
side
frame
using
appropriate
timbers
so
as
not
to
deform
or
damage
the
sur
-
face
of
the
structure
.
21
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals