GE POWER/VAC 4.16 - Primary Disconnects; Breaker Racking Mechanism; Remote Racking Operator

GE POWER/VAC 4.16
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
accessory
with
each
Power
/
Vac
*
switchgear
order
(
Fig
.
10
)
.
This
accessory
device
is
used
to
elevate
the
breaker
from
the
floor
or
working
platform
to
the
level
of
the
tracks
in
the
switchgear
cubicle
.
Docking
of
the
lifting
device
rails
to
the
switchgear
tracks
is
provided
for
maximum
safety
.
(
See
OPERATION
REMOVAL
,
PAGE
36
OR
GEK
90214
)
.
BREAKER
INSTALLATION
AND
BREAKER
RACKING
MECHANISM
When
installed
in
the
switchgear
cubicle
,
the
removable
element
is
supported
by
two
horizontal
steel
tracks
,
one
on
each
side
of
the
cubicle
.
The
racking
mechanism
moves
the
breaker
element
along
these
tracks
between
the
connected
and
test
positions
.
This
mechanism
consists
of
heavy
-
duty
steel
jack
screws
which
carry
nuts
that
engage
the
sides
of
the
removable
element
.
The
racking
mechanism
may
be
man
-
ually
operated
with
the
racking
handle
which
is
furnished
with
each
equipment
.
The
breaker
cannot
be
moved
between
the
connected
and
test
/
disconnect
positions
unless
it
has
been
tripped
.
The
breaker
cannot
be
closed
unless
it
is
in
the
connected
or
test
/
disconnect
position
.
For
a
detailed
explanation
of
the
racking
mechanism
refer
to
description
under
OPERATION
CLOSED
DOOR
BREAKER
RACKING
,
PAGE
39
.
1
1200
AMP
REMOTE
RACKING
OPERATOR
The
optional
electrically
operated
racking
device
(
see
Fig
.
11
)
provides
a
convenient
means
for
racking
a
breaker
be
-
tween
the
connected
and
test
positions
from
a
remote
loca
-
tion
.
It
is
easily
mounted
to
the
breaker
unit
front
door
and
is
designed
for
quick
transfer
between
units
.
The
remote
racking
operator
is
furnished
in
two
operat
-
ing
voltage
versions
.
The
115
V
AC
,
50
/
60
hertz
model
has
a
four
foot
electrical
cord
with
standard
three
prong
plug
to
fit
a
grounded
receptacle
or
extension
cord
.
The
230
VAC
,
50
/
60
hertz
model
has
a
three
wire
four
foot
cord
to
which
the
purchaser
applies
his
standard
plug
.
The
remote
racking
operator
is
provided
with
a
two
posi
-
tion
directional
switch
,
an
On
-
Off
circuit
breaker
and
a
push
button
control
box
attached
with
a
30
foot
extension
cord
.
2
2000
AMP
Instructions
for
the
remote
racking
operator
are
found
in
GEK
86130
(
115
VAC
)
&
GEK
86131
(
230
VAC
)
.
PRIMARY
DISCONNECTS
The
1200
and
2000
ampere
primary
disconnects
consist
of
two
rows
of
silver
-
plated
copper
fingers
mounted
on
either
side
of
the
circuit
breaker
studs
.
These
fingers
are
held
in
place
with
a
spider
which
positions
the
fingers
and
fastens
them
to
the
breaker
.
Wipe
pressure
is
obtained
by
tension
springs
between
the
rows
of
fingers
which
pull
them
to
-
gether
.
When
the
circuit
breaker
is
connected
to
the
metal
-
3
_
3000
AMP
Primary
Disconnects
18
Courtesy of NationalSwitchgear.com