EasyManua.ls Logo

GE POWER/VAC 4.16 - Cable Terminations (Potheads); Cable Terminations (Without Pothead); Ground Fault Current Transformers

GE POWER/VAC 4.16
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
POTHEADS
GROUND
FAULT
CURRENT
TRANSFORMERS
(
THROUGH
-
TYPE
)
Installation
procedures
for
a
three
-
conductor
lead
-
sheathed
cable
with
a
wiping
sleeve
cable
entrance
Fitting
on
the
pothead
are
outlined
in
Russgreen
Cat
.
No
.
P
66
.
This
is
the
type
most
generally
used
.
The
factory
does
not
furnish
insulating
materials
for
completing
stress
cones
and
cable
terminations
.
In
all
cases
,
carefully
follow
the
cable
manu
-
facturer
s
recommendation
for
installation
of
the
type
cable
being
used
.
Through
-
type
current
transformers
(
see
Fig
.
35
)
are
furnished
where
specified
for
sensitive
protection
against
ground
faults
.
These
transformers
are
normally
installed
in
a
horizontal
position
directly
above
or
below
the
primary
cable
terminals
so
that
the
primary
cable
or
cables
can
pass
through
them
.
One
transformer
is
required
for
each
three
-
phase
circuit
.
Where
armored
cable
is
used
,
the
armor
must
be
termin
-
ated
and
grounded
before
the
cable
passes
through
the
transformer
.
Armor
clamps
are
furnished
for
this
purpose
when
specified
.
TERMINATION
WITHOUT
POTHEAD
The
factory
does
not
furnish
insulating
materials
for
com
-
pleting
the
termination
of
primary
cables
,
nor
does
it
furnish
stress
cone
material
.
The
cable
manufacturer
s
recommen
-
dations
should
be
followed
for
the
type
of
cable
being
used
.
When
stress
cones
are
required
,
packaged
stress
cone
kits
such
as
the
GE
Termi
-
Maticrr
Cable
Termination
System
are
frequently
used
.
Information
and
ordering
data
can
be
found
in
GEA
-
1017
.
Since
the
termination
is
inside
the
metal
-
clad
enclosure
,
the
Indoor
Type
A
system
is
generally
applicable
.
If
excessive
contamination
is
a
problem
,
the
padmount
type
G
system
may
be
desirable
.
No
matter
which
system
is
used
,
step
-
by
-
step
pictorial
instructions
will
be
furnished
as
part
of
the
kit
.
The
space
provided
for
primary
cable
terminations
in
the
standard
Power
-
Vac
arrangements
is
more
than
sufficient
for
the
Termi
-
MaticT
system
.
Hand
-
taped
stress
cones
require
more
space
.
However
,
the
cable
termination
space
provided
in
Power
/
Vac
*
is
never
less
than
the
minimum
recommended
for
a
hand
-
taped
stress
cone
.
«
r
-
CN
In
making
up
stress
cone
terminations
,
ground
clamps
and
ground
leads
are
installed
.
Care
must
be
taken
to
assure
that
these
grounded
elements
are
installed
such
that
the
required
clearance
to
energized
parts
is
maintained
.
For
insulated
bars
or
unshielded
cables
,
these
are
s
oo
oc
U
-
For
5
kV
equipments
at
least
2
inches
For
15
kV
equipments
at
least
3
inches
When
terminating
three
conductor
cables
which
flare
out
to
single
conductor
terminations
,
the
crotch
at
the
root
of
the
flare
-
out
should
be
adequately
sealed
to
prevent
possible
entrance
of
moisture
into
the
three
conductor
jackets
.
Fig
.
35
Rear
View
of
Unit
Showing
Through
-
Type
Ground
Fault
Current
Transformers
For
long
cable
runs
within
the
equipment
,
a
support
to
restrain
lateral
movement
of
the
cables
under
short
circuit
conditions
will
be
provided
approximately
20
inches
from
the
termination
point
.
The
customer
s
incoming
cables
should
be
lashed
securely
to
this
support
.
There
is
no
provision
in
the
Power
/
Vac
*
equipment
to
support
the
weight
of
primary
cables
.
t
34
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals