EasyManua.ls Logo

GE POWER/VAC 4.16 - Positive Interlock; Negative Interlock

GE POWER/VAC 4.16
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
After
the
breaker
has
been
racked
fully
into
the
connected
position
and
then
is
removed
from
the
unit
,
the
engagement
and
alignment
of
the
primary
disconnect
fingers
on
the
breaker
studs
may
be
checked
with
respect
to
the
stationary
^
conductor
in
the
unit
.
(
THE
SWITCHGEAR
MUST
BE
WDE
-
ENERGIZED
FOR
THIS
CHECK
.
)
REMOTE
RACKING
ATTACHMENT
The
breaker
can
be
racked
between
the
Disconnect
/
Test
and
Connected
positions
electrically
using
the
remote
racking
device
.
See
DESCRIPTION
REMOTE
RACKING
ATTACHMENT
.
POSITIVE
INTERLOCK
Use
the
racking
handle
to
turn
the
jackscrew
several
turns
toward
the
connected
position
,
until
the
shutters
are
opened
to
uncover
the
opening
to
the
insulation
tube
and
stationary
conductor
in
the
unit
.
Inspect
the
impression
made
in
the
coating
of
contact
lubricant
0282
A
2048
P
009
in
the
station
-
ary
conductor
surface
by
the
breaker
primary
disconnect
fingers
.
On
1200
and
2000
ampere
ratings
,
there
must
be
heavy
impressions
of
all
the
lingers
on
both
the
top
and
bottom
of
the
stationary
conductor
bar
.
The
impression
should
extend
back
from
the
front
end
of
the
bar
a
minimum
of
1
/
2
inch
and
should
be
no
closer
than
3
/
16
inch
to
either
side
of
the
bar
.
The
positive
interlock
functions
to
prevent
racking
a
breaker
between
the
Connect
and
Disconnect
/
Test
positions
except
when
the
primary
contacts
are
open
.
The
positive
interlock
consists
of
a
bar
which
protrudes
from
the
left
side
of
a
closed
breaker
to
engage
a
slot
in
the
left
-
side
racking
mechanism
when
the
breaker
is
in
either
the
Disconnect
/
Test
or
Connected
position
.
When
the
interlock
is
engaged
the
racking
mechanism
can
-
not
be
operated
(
See
Fig
.
40
.
)
To
test
the
function
of
the
positive
interlock
install
a
circuit
breaker
following
the
instructions
given
under
BREAKER
INSTALLATION
.
For
the
test
the
control
power
circuits
in
the
metal
-
clad
must
be
energized
.
Place
the
breaker
in
the
Disconnect
/
Test
position
and
connect
the
secondary
disconnect
device
by
pulling
down
on
the
breaker
handle
and
horizontally
inserting
the
lever
arm
fully
into
the
breaker
to
engage
the
secondary
disconnects
.
This
will
actuate
the
spring
-
charging
motor
and
charge
the
breaker
-
closing
springs
.
BEFORE
PROCEEDING
WITH
THIS
CHECK
,
IT
IS
NECESSARY
THAT
THE
PRI
-
MARY
CIRCUITS
BE
DE
-
ENERGIZED
.
Close
the
breaker
with
the
control
switch
on
the
front
of
the
door
then
attempt
to
insert
the
racking
handle
into
the
hole
in
the
unit
door
.
A
definite
stop
should
be
encountered
,
preventing
the
socket
on
the
racking
handle
from
engaging
the
racking
mechanism
.
On
3000
ampere
ratings
,
there
must
be
heavy
impressions
of
all
the
fingers
on
the
cylindrical
conductor
.
The
impres
-
sions
should
extend
back
from
the
front
end
a
minimum
of
1
/
2
inch
.
IF
THE
CONTACT
WIPE
IS
NOT
PROPER
,
DO
NOT
MAKE
ANY
ADJUSTMENT
.
COMMUNICATE
WITH
THE
NEAREST
GENERAL
ELECTRIC
COMPANY
APPARATUS
AND
SERVICE
ENGINEERING
OF
-
FICE
FOR
INSTRUCTIONS
.
#
BREAKER
RACKING
WITH
FRONT
DOOR
CLOSED
The
circuit
breaker
can
be
racked
in
and
out
of
the
Connect
position
with
the
front
door
of
the
metal
-
clad
closed
.
For
maximum
safety
the
breaker
must
always
be
racked
with
the
front
door
closed
when
primary
power
is
connected
to
the
metal
-
clad
.
Make
sure
the
breaker
is
open
before
attempting
to
rack
the
breaker
.
The
breaker
is
in
-
stalled
in
the
metal
-
clad
unit
as
described
in
BREAKER
INSTALLATION
.
Engage
the
racking
arms
and
then
close
the
front
door
of
the
unit
and
secure
it
.
Insert
the
racking
handle
into
the
hole
in
the
left
side
of
the
front
door
and
engage
the
racking
mechanism
by
pushing
it
in
fully
.
Rack
the
breaker
by
rotating
the
handle
clockwise
(
60
turns
are
required
)
until
a
positive
stop
is
felt
.
The
breaker
is
now
in
the
fully
connected
position
and
the
tape
indicator
should
read
Conn
.
Trip
the
breaker
and
rack
it
into
the
connected
position
.
THE
PRIMARY
CIRCUITS
MUST
BE
DE
-
ENERGIZED
BEFORE
MAKING
THIS
CHECK
OF
THE
POSITIVE
INTERLOCK
.
Close
the
breaker
and
attempt
to
insert
the
racking
handle
into
the
hole
in
the
unit
door
.
A
definite
stop
should
be
encountered
,
preventing
the
socket
on
the
racking
handle
from
engaging
the
racking
mechanism
.
If
the
interlock
does
not
function
as
indicated
in
either
of
the
above
cases
DO
NOT
MAKE
ANY
ADJUSTMENT
.
COMMUNICATE
WITH
THE
NEAREST
GENERAL
ELECTRIC
COMPANY
APPARATUS
AND
SERVICE
ENGINEERING
OFFICE
FOR
INSTRUCTIONS
.
NEGATIVE
INTERLOCK
DO
NOT
EXCEED
60
FT
.
LBS
.
TORQUE
.
The
negative
interlock
functions
to
hold
the
breaker
in
a
mechanical
and
electrical
trip
-
free
mode
when
it
is
being
racked
between
the
Disconnect
/
Test
and
Connect
posi
-
tions
.
As
an
added
precaution
,
the
negative
interlock
will
trip
the
breaker
and
hold
it
trip
-
free
if
an
attempt
is
made
to
To
rack
the
circuit
breaker
from
the
Connected
to
the
Disconnect
/
Test
position
be
sure
that
the
breaker
is
open
then
turn
the
handle
counterclockwise
.
§
39
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals