Chapter 3: Configuration
GFK-2958E RSTi-EP User Manual 42
Ch 0 ... Ch 1: Comparison
function
disabled (0) / higher
equal comparison
value (1) / lower
equal comparison
value (2)/ equal
comparison value (3)
disabled
Ch 0 ... Ch 1: Counter dir. signal
B inv.
disabled (0) /
enabled (1)
disabled
Ch 0 ... Ch 1: Signal mode
Rotary transducer -
single (0) / Rotary
transducer - double
(1) / Rotary
transducer -
quadruple (2) / Pulse
and Direction (3) /
disabled (4)
disabled
Ch 0 ... Ch 1: Counter behavior
internal gate
Interrupt counting (0)
/ Cancel counting (1)
interrupt counting
Ch 0 ... Ch 1: Set value
-2147483648 ...
2147483647
0
Ch 0 ... Ch 1: End value
-2147483648 ...
2147483647
2147483647
Ch 0 ... Ch 1: Load value
-2147483648 ...
2147483647
0
Ch 0 ... Ch 1: Hysteresis
0 ... 255
0
Product
Part No.
Parameter
Optional values
Default value
2 Channel Frequency
Measurement, 100
kHz
EP-5212
Ch 0 ... Ch 1: Input filter
5 μs [187 kHz] (0) /
11 μs [94 kHz] (1) /
21 μs [47 kHz] (2) /
43 μs [23 kHz] (3) /
83 μs [12 kHz] (4) /
167 μs [6 kHz] (5) /
333 μs [3 kHz] (6) /
667 μs [1,5 kHz] (7) /
1 ms [732 Hz] (8) /
3 ms [366 Hz] (9) /
5 ms [183 Hz] (10) /
11 ms [92 Hz] (11) /
22 ms [46 Hz] (12) /
43 ms [23 Hz] (13) /
91 ms [11 Hz] (14) /
167 ms [6 Hz] (15) /
333 ms [3 Hz] (16)
5 μs [187 kHz]
Product
Part No.
Parameter
Optional values
Default value
2 Channels PWM
Output, Positive
Logic, 24VDC, 0.5 A
2 Channels PWM
Output, Positive
Logic, 24VDC, 2 A
EP-5422
EP-5442
Ch 0 … Ch 1: Period duration =
n*20,83 ns
1202 ... 8388607
1202
Product
Part No.
Parameter
Optional values
Default value
Analog Input, 4
Channels Voltage/
EP-3164
Frequency suppression
disabled (0) / 50 Hz (1)
/ 60 Hz (2) / Average
over 16 values (3)
disabled

Table of Contents