GFK-1504N Chapter 1 Introduction 1-19
1
VersaMax General Product Specifications
VersaMax products should be installed and used in conformance with product-
specific guidelines, as well as the specifications listed in the following table.
Environmental
Vibration
IEC68-2-6
1G at 57-150Hz, 0.012in p--p at 10-57Hz
Shock
IEC68-2-27
15G, 11ms
Operating Temperature
0 to +60 deg C ambient
-40 to +60 deg C ambient for I/O carriers,
communications carrier, interposing I/O terminals, and
auxiliary I/O terminals
Storage Temperature
-40 to +85 deg C
Humidity
5% to 95%, noncondensing
Enclosure Protection IEC529 Steel cabinet per IP54:
protection from dust & splashing water
EMC Emission
Radiated, Conducted CISPR 11/EN 55011 Industrial Scientific & Medical Equipment
(Group 1, Class A)
CISPR 22/EN 55022
Information Technology Equipment (Class A)
FCC 47 CFR 15 Referred to as FCC part 15,
Radio Devices (Class A)
EMC Immunity
Electrostatic Discharge
EN 61000-4-2
8KV Air, 4KV Contact
RF Susceptibility EN 61000-4-3 10V
rms
/m, 80 to 1000Mhz, 80% AM
ENV 50140/ENV 50204 10V
rms
/m, 900MHz ±5MHZ
100%AM with 200Hz square wave
Fast Transient Burst
EN 61000-4-4
2KV: power supplies, 1KV: I/O, communication
Surge Withstand ANSI/IEEE C37.90a Damped Oscillatory Wave: 2.5KV:
power supplies, I/O [12V-240V]
IEC255-4 Damped Oscillatory Wave: Class II,
power supplies, I/O [12V-240V]
EN 61000-4-5 2 kV cm(P/S); 1 kV cm (I/O and communication
modules)
Conducted RF EN 61000-4-6 10V
rms
, 0.15 to 80Mhz, 80%AM
Isolation
Dielectric Withstand
UL508, UL840, IEC664
1.5KV for modules rated from 51V to 250V
Power Supply
Input Dips, Variations EN 61000-4-11 During Operation: Dips to 30% and 100%,
Variation for AC ±10%,
Variation for DC ±20%

Table of Contents