GFK-1504N Chapter 1 Introduction 1-19
VersaMax General Product Specifications
VersaMax products should be installed and used in conformance with product-
specific guidelines, as well as the specifications listed in the following table.
1G at 57-150Hz, 0.012in p--p at 10-57Hz
Operating Temperature
-40 to +60 deg C ambient for I/O carriers,
communications carrier, interposing I/O terminals, and
Enclosure Protection IEC529 Steel cabinet per IP54:
protection from dust & splashing water
Radiated, Conducted CISPR 11/EN 55011 Industrial Scientific & Medical Equipment
Information Technology Equipment (Class A)
FCC 47 CFR 15 Referred to as FCC part 15,
RF Susceptibility EN 61000-4-3 10V
/m, 80 to 1000Mhz, 80% AM
ENV 50140/ENV 50204 10V
rms
/m, 900MHz ±5MHZ
100%AM with 200Hz square wave
2KV: power supplies, 1KV: I/O, communication
Surge Withstand ANSI/IEEE C37.90a Damped Oscillatory Wave: 2.5KV:
power supplies, I/O [12V-240V]
IEC255-4 Damped Oscillatory Wave: Class II,
power supplies, I/O [12V-240V]
EN 61000-4-5 2 kV cm(P/S); 1 kV cm (I/O and communication
Conducted RF EN 61000-4-6 10V
, 0.15 to 80Mhz, 80%AM
1.5KV for modules rated from 51V to 250V
Input Dips, Variations EN 61000-4-11 During Operation: Dips to 30% and 100%,
Variation for AC ±10%,