GFK-1504N Chapter 10 Analog Input Modules 10-41
IC200ALG264, IC200ALG266: Analog Input Module, 15 Bit Current 15 Channels
Configuration Parameters
A jumper on the carrier terminals can be used to configure 4-20mA or 0-20mA
input ranges. With no jumper installed, the module accepts 4-20mA input
signals. With a jumper installed, the module accepts 0-20mA input signals.
The analog inputs are software-configurable to either default or hold last state
upon loss of module.
Module Specifications
15 single ended, one group
Module ID FFFFB50F (when cfg for 4-20mA range)
FFFFB40F (when cfg for 0-20mA range)
Isolation:
User input to logic (optical) and
to frame ground
Group to group
250 V AC continuous; 1500 V AC for 1 minute
Not applicable
OK LED. See "LED Indicators" for description.
Backplane current consumption
IC200ALG264: 5V = 100mA maximum
IC200ALG266: 5V = 100mA, +3.3V = 50mA maximum
Range select (jumpers on carrier)
Loss of Internal Power, Open wire detection of 4-20mA
signals only. Module IC200ALG266 only: A/D conversion
malfunction greater than 6% full scale.
Compatibility
PME programming
software
001
002
005
E05
001
001
001
001
HW, FW version
All
No
4 to 20mA (default : no terminal jumper installed)
0 to 20mA (with terminal jumper installed)
IC200ALG264: +3V; IC200ALG266: +30V
25 °C
†
±0.3% typical of full scale, ±0.5% maximum of full scale
±1% maximum of full scale
0.5µA = 1 counts (for 4-20mA range)
0.625µA = 1 counts (for 0-20mA range)
Filter response (3dB Corner Freq)
†
In the presence of severe RF interference, (IEC 1000-4-3, 10V/m), accuracy may be degraded
to ±2%.