ZP3 Fire Control Panel User Guide
Reports to printer
Menu path Operator/Reports to printer
Purpose This menu provides a selection of reports to print.
Archives This option allows you to print previous alarms and events, which are stored as "archives"
in the panel. The panel automatically stores the last 484 panel events, together with the
date and time of each event. These events may be selected by date. The printout includes
all event types configured for the printer.
Point status This option allows you to print the status of any device attached to the panel Z-loops. The
printer can also be stopped from this menu.
Stop printer This menu option allows you to end the current print operation.
Lamp test
Menu path Operator/Lamp test
Purpose This function illuminates all panel fascia LED's for a short period, including the display,
allowing the operator to verify that they are functional.
Keypad test
Menu path Operator/Keypad test
Purpose This menu initiates a Keypad test. Once selected, the panel reports any key pressed on
the panel via the LCD. The operator can use this function to check that the keypad is
functional. Press any key twice to exit.
Page 24 Revision 11 (05/01/2010)