IV. Water Calculations
Please Note
Utilize this worksheet to perform calculations at project site to determine residual water that
will be captured by Dropmaster tank before placing Dropmaster in service.
1 Gallon of water = 8.344 lbs.
Pressure Vacuum
1 psi = 2.036 inches H.G.
5 psi = 10.18 inches H.G.
10 psi = 20.36 inches H.G.
15 psi = 30.54 inches H.G.
Water in Pipes By Size
Pipe Size Schedule 40 Schedule 10
1” per foot .045 .049
1 ¼” per foot .078 .085
1 ½” per foot .106 .115
2” per foot .174 .190
2 ½” per foot .248 .283
3” per foot .383 .433
4” per foot .660 .740
6” per foot 1.501 1.649