N.B.: for the version R77 are not available the probe codes 0...39, 48...51, 54...58
In case of probe non-availability, maximum and minimum limits are set to 0.
In case of custom linearization, test limits for setting LO and HI errors are given by the calibration values.
If these limits are not exceeded, they are taken into consideration as limits L_S and H_S.
Select sampling time 
(resolution). For linear 
input 0...1V/POT only.
  0  120ms  > 14bit; 16000 divs
  1  60ms  > 14bit; 16000 divs
  2  30ms  > 13bit; 8000 divs
  3  15ms  > 12bit; 4000 divs
 TYPE
  Type  4 DIGIT
    PROBE
      without dec. point  with dec. point
  Probe: TC
  0  TC J °C  0/1000  0.0/999.9
  1  TC J °F  32/1832  32.0/999.9
  2  TC K °C  0/1300  0.0/999.9
  3  TC K °F  32/2372  32.0/999.9
  4  TC R °C  0/1750  0.0/999.9
  5  TC R °F  32/3182  32.0/999.9
  6  TC S °C  0/1750  0.0/999.9
  7  TC S °F  32/3182  32.0/999.9
  8  TC T °C  -200/400  -199.9/400.0
  9  TC T °F  -328/752  -199.9/752.0
 10  TC B °C  44/1800  44.0/999.9
 11  TC B °F  111/3272  111.0/999.9
 12  TC E °C  -100/750  -100.0/750.0
 13  TC E °F  -148/1382  -148.0/999.9
 14  TC N °C  0/1300  0.0/999.9
 15  TC N °F  32/2372  32.0/999.9
 16  TC L °C  0/600  0.0/600.0
 17  TC L °F  32/1112  32.0/999.9
 18  TC U °C  -200/400  -199.9/400.0
 19  TC U °F  -328/752  -199.9/752.0
 20  TC G °C  0/2300  0.0/999.9
 21  TC G °F  32/4172  32.0/999.9
 22  TC D °C  0/2300  0.0/999.9
 23  TC D °F  32/4172  32.0/999.9
 24  TC C °C  0/2300  0.0/999.9
 25  TC C °F  32/4172  32.0/999.9
 26  TC °C  Custom  Custom
 27  TC °F  Custom  Custom
  Probe: RTD
 28  PT100 °C  -200/600   -199.9/600.0
 29  PT100 °F  -328/1112  -199.9/999.9
 30  JPT100 °C  -200/600   -199.9/600.0
 31  JPT100 °F  -328/1112  -199.9/999.9
    Probe: PTC - NTC
 32  PTC °C  -55/120    -55.0/120.0
 33  PTC °F  -67/248    -67.0/248.0
 34  NTC °C  -10/70    -10.0/70.0
 35  NTC °F  14/158    14.0/158.0
    Probe: Voltage + Current
 36  0...60mV  -1999/9999  -199.9/999.9
 37  0...60mV  custom linear  custom linear
 38  12...60mV  -1999/9999  -199.9/999.9
 39  12...60mV  custom linear  custom linear
 40  0...20mA  -1999/9999  -199.9/999.9
 41  0...20mA  custom linear  custom linear
 42  4...20mA  -1999/9999  -199.9/999.9
 43  4...20mA  custom linear  custom linear
 44  0...10V  -1999/9999  -199.9/999.9
 45  0...10V  custom linear  custom linear
 46  2...10V  -1999/9999  -199.9/999.9
 47  2...10V  custom linear  custom linear
 48  0...5V  -1999/9999  -199.9/999.9
 49  0...5V  custom linear  custom linear
 50  1...5V  -1999/9999  -199.9/999.9
 51  1...5V  custom linear  custom linear
 52  0...1V/Pot  -1999/9999  -199.9/999.9
 53  0...1V/Pot  custom linear  custom linear
 54  200mV...1V  -1999/9999  -199.9/999.9
 55  200mV...1V  custom linear  custom linear
    Probe: Custom   PT100 - PTC - NTC
 56  PT100  custom    custom
    JPT
 57  PTC  custom    custom
 58  NTC  custom    custom
• TC/LIN input parameters
Input settings
Type of probe, 
signal and scale of 
main input
+4 to disable filter
(average of the last eight values sampled)
Max. non-linearity error for
thermocouples (TC),
resistors (PT100) and
thermistors (PTC, NTC).
The error is calculated as
deviation from theoretical value
and is expressed as percentage of full 
scale (in °C).
 S, R  range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other range; error < 0.5% f.s.
 T  error < 0.2% f.s. (t > -150°C)
 B  range 44...1800°C; error < 0.5% f.s. (t > 300°C) / range 44,0...999,9; error < 1% f.s. (t > 300°C)
 U  range -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other range; error < 0.2% f.s. (t > -150°C)
 G  error < 0.2% f.s. (t > 300°C)
 D  error < 0.2% f.s. (t > 200°C)
 C  range 0...2300; error < 0.2% f.s. / for other range; error < 0.5% f.s.
 NTC  error < 0.5% f.s.
 Tc J, K, E, N, L  error < 0.2% f.s.
 PT100, JPT100 e PTC  error < 0.2% f.s.
In
t.P
(.1.
4
81600G_MHW_4T48_07-2011_ENG
                               4 / 7