N.B.: for the version R77 are not available the probe codes 0...39, 48...51, 54...58
In case of probe non-availability, maximum and minimum limits are set to 0.
In case of custom linearization, test limits for setting LO and HI errors are given by the calibration values.
If these limits are not exceeded, they are taken into consideration as limits L_S and H_S.
Select sampling time
(resolution). For linear
input 0...1V/POT only.
0 120ms > 14bit; 16000 divs
1 60ms > 14bit; 16000 divs
2 30ms > 13bit; 8000 divs
3 15ms > 12bit; 4000 divs
TYPE
Type 4 DIGIT
PROBE
without dec. point with dec. point
Probe: TC
0 TC J °C 0/1000 0.0/999.9
1 TC J °F 32/1832 32.0/999.9
2 TC K °C 0/1300 0.0/999.9
3 TC K °F 32/2372 32.0/999.9
4 TC R °C 0/1750 0.0/999.9
5 TC R °F 32/3182 32.0/999.9
6 TC S °C 0/1750 0.0/999.9
7 TC S °F 32/3182 32.0/999.9
8 TC T °C -200/400 -199.9/400.0
9 TC T °F -328/752 -199.9/752.0
10 TC B °C 44/1800 44.0/999.9
11 TC B °F 111/3272 111.0/999.9
12 TC E °C -100/750 -100.0/750.0
13 TC E °F -148/1382 -148.0/999.9
14 TC N °C 0/1300 0.0/999.9
15 TC N °F 32/2372 32.0/999.9
16 TC L °C 0/600 0.0/600.0
17 TC L °F 32/1112 32.0/999.9
18 TC U °C -200/400 -199.9/400.0
19 TC U °F -328/752 -199.9/752.0
20 TC G °C 0/2300 0.0/999.9
21 TC G °F 32/4172 32.0/999.9
22 TC D °C 0/2300 0.0/999.9
23 TC D °F 32/4172 32.0/999.9
24 TC C °C 0/2300 0.0/999.9
25 TC C °F 32/4172 32.0/999.9
26 TC °C Custom Custom
27 TC °F Custom Custom
Probe: RTD
28 PT100 °C -200/600 -199.9/600.0
29 PT100 °F -328/1112 -199.9/999.9
30 JPT100 °C -200/600 -199.9/600.0
31 JPT100 °F -328/1112 -199.9/999.9
Probe: PTC - NTC
32 PTC °C -55/120 -55.0/120.0
33 PTC °F -67/248 -67.0/248.0
34 NTC °C -10/70 -10.0/70.0
35 NTC °F 14/158 14.0/158.0
Probe: Voltage + Current
36 0...60mV -1999/9999 -199.9/999.9
37 0...60mV custom linear custom linear
38 12...60mV -1999/9999 -199.9/999.9
39 12...60mV custom linear custom linear
40 0...20mA -1999/9999 -199.9/999.9
41 0...20mA custom linear custom linear
42 4...20mA -1999/9999 -199.9/999.9
43 4...20mA custom linear custom linear
44 0...10V -1999/9999 -199.9/999.9
45 0...10V custom linear custom linear
46 2...10V -1999/9999 -199.9/999.9
47 2...10V custom linear custom linear
48 0...5V -1999/9999 -199.9/999.9
49 0...5V custom linear custom linear
50 1...5V -1999/9999 -199.9/999.9
51 1...5V custom linear custom linear
52 0...1V/Pot -1999/9999 -199.9/999.9
53 0...1V/Pot custom linear custom linear
54 200mV...1V -1999/9999 -199.9/999.9
55 200mV...1V custom linear custom linear
Probe: Custom PT100 - PTC - NTC
56 PT100 custom custom
JPT
57 PTC custom custom
58 NTC custom custom
• TC/LIN input parameters
Input settings
Type of probe,
signal and scale of
main input
+4 to disable filter
(average of the last eight values sampled)
Max. non-linearity error for
thermocouples (TC),
resistors (PT100) and
thermistors (PTC, NTC).
The error is calculated as
deviation from theoretical value
and is expressed as percentage of full
scale (in °C).
S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other range; error < 0.5% f.s.
T error < 0.2% f.s. (t > -150°C)
B range 44...1800°C; error < 0.5% f.s. (t > 300°C) / range 44,0...999,9; error < 1% f.s. (t > 300°C)
U range -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other range; error < 0.2% f.s. (t > -150°C)
G error < 0.2% f.s. (t > 300°C)
D error < 0.2% f.s. (t > 200°C)
C range 0...2300; error < 0.2% f.s. / for other range; error < 0.5% f.s.
NTC error < 0.5% f.s.
Tc J, K, E, N, L error < 0.2% f.s.
PT100, JPT100 e PTC error < 0.2% f.s.