26 • Commissioning OptiMove CR07
System parameter P1: setting the upper stroke
limit
If the axis control unit operates with a Gema axis, all system parameters
are already set to the values for this axis. The only system parameter to
be set is the upper stroke limit.
The maximum stroke height (max. travel) is limited by the upper stroke
limit. The maximum stroke height is limited by the corresponding height
of the used reciprocator or by the maximum height of the gun slots in the
booth. The upper stroke limit of the OptiMove CR07 Axis control unit is
always set at 0.3 meters by the factory.
In order to set the upper stroke limit (system parameter 1), proceed as
follows:
1. To enter the system parameter mode, press and hold the
key for 5 seconds.
The LEDs L1-L3 illuminate
2. Select the parameter P1 on the display A1 by using the
keys
3. Set the upper stroke limit value on the display A2 using the
keys
WARNING:
Always pay attention to the gun positions and the maximum height
of the gun slots in the booth! If an incorrect (too high) stroke limit is
set, this can lead to damage to the axis and/or the booth!
4. Press the key, in order to exit the system parameter mode