50 CAN bus OptiMove CR07
Setting the user address (ID Number)
1. To enter the system parameter mode, press and hold the
key for 5 seconds. The LEDs L1-L3 illuminate
2. Select the parameter P12 on the display A1 by using the
keys
3. Select an address between 1 and 127 on the display A2 using
the
keys
4. Press the
key, in order to exit the system parameter mode
WARNING:
The selected address in the system parameter P12 may never be
"0", the address must be unique and may not conflict with the
numbers of other existing users!
Setting the Baud rate
1. To enter the system parameter mode, press and hold the
key for 5 seconds. The LEDs L1-L3 illuminate
2. Select the parameter P11 on the display A1 by using the
keys
3. Select a value between 0 and 7 on the display A2 using the
keys
Set value - P11 CAN Baud rate
0 20 kBit/s
1 50 kBit/s
2 100 kBit/s
3 125 kBit/s (Default)
4 250 kBit/s
5 500 kBit/s
6 800 kBit/s
7 1 Mbit/s
The Baud rate is selected with 125 kBits as default. This setting permits a
maximum cable length of approx. 500 m from the first to the last CAN bus
client. If longer cables are used, select a lower Baud rate.
4. Press the
key, in order to exit the system parameter mode