Inspection and maintenance 11
0020229560_00 Betacom 3 Installation and maintenance instructions 23
Checking the CO content
Great Bri-
tain
Removed
front cas-
ing/installed
front casing
Natural gas
G20
9.2 ±1 %
The value is OK.
The value is not OK; you cannot start up the
product.
Set the CO content. ( Page 23)
11.4 Setting the CO content
Conditions: The CO content must be adjusted
1
Turn the screw (1) to set the CO content (value with
front casing removed).
To increase the CO content: Turn anti-clockwise
To decrease the CO content: Turn clockwise
Only carry out the adjustment in increments of 1/8 turn
and wait approximately 1 minute after each adjustment
until the value has stabilised.
Compare the measured value with the corresponding
value in the table.
Setting the CO value
Great Britain
Removed front cas-
ing/installed front
casing
Natural gas
G20
CO at full
load
9.2 ±0.2 %
Set for
Wobbe
index W
14.09 kWh/m³
O at full
load
4.5 ±1.8 vol. %
CO at full
load
250 ppm
CO/CO
0.0027
If the setting is not in the specified adjustment range,
you must not start up the product.
Inform Customer Service.
Check whether the air-quality requirements with regard
to carbon monoxide are fulfilled.
Install the front casing.
11.5 Removing the gas-air mixture unit
Note
The gas-air mixture unit consists of three main
components:
Ventilator
Gas valve,
Burner cover
1. Switch off the product via the main switch.
2. Close the gas isolator cock.
3. Remove the front casing. ( Page 10)
B
A
1
C
2
4. Push the clip (1) upwards.
5. Remove the flue pipe (2).
3
4
5
A
B
6. Remove the air intake pipe (3).
7. Remove the plugs from the gas valve (4) and from the
fan (5).