Diagram 5.9
AIR DUCT /
TERMINAL ASSEMBLY
Diagram 5.10
FLUE ELBOW ASSEMBLY
5 Preparation
FLUE
DUCT
AIR DUCT / TERMINAL
ASSEMBLY
3mm
DRILL SIZE
SEAL WITH
TAPE SUPPLIED
AIR DUCT/TERMINAL &
FLUE DUCT ASSEMBLY
FLUE ELBOW
ASSEMBLY
REAR FLUE
SECURING POINTS
SIDE FLUE
SECURING POINTS
LHD/RHD
LHD
RHD
5.10 Internal Flue Installation
If access to the outside wall is not practical, the flue system can
be installed from inside. Use of the optional wall liner kit
recommended.
Secure the flue elbow to the air duct/terminal with the two self
tapping screws supplied in the fittings pack, see diagram 5.10.
Place the sealing tape from the fittings pack around the flue
elbow as diagram 5.10.
Place the flue assembly to one side until required.
Continue at “Boiler Preparation”.
5.11 Wall Liner
If a wall liner is used, fit self adhesive seal as follows:
For wall thicknesses up to 300mm fit the self adhesive seal to the
air duct, see diagram 5.11, make sure the joint is on top.
For wall thicknesses over 300mm see diagram 5.12..
When installed the seal will be within the wall.
3293
3294
Diagram 5.11
FOAM SEAL
(Wall Thickness up to 300mm)
*Increase dimension by 15mm if the
“Optional Flue Collar” is to be fitted.
*
10mm
FOAM SEAL
Q
6896