24
220692C
24
SECTION
Installation
6
step
9
3043
step
10
step
11
RIGHT HAND
FLUE HOOD
ASSEMBLY
Side Flue Boiler
Installation
Remove the appropriate blanking plate
on the casing and fit it to the rear flue
outlet.
Remove the fan assembly from the
fluehood assembly, by removing the
two screws.
Partially refit the securing screws into
the fan.
Turn the fan assembly to the required
flue outlet direction.
Fit the flue hood over the partially
fitted securing screws in the special
key hole slot sandwiching the gaskets
and spacer between, take care not to
damage the gaskets.
Turn the flue hood in the direction
shown.
Remove and discard the fan rear
outlet extension from the fan by
releasing the clip.
Fit the fan side outlet extension,
supplied in the loose items pack.
Secure with the clip previously
removed.
REAR VIEW
GASKET
BLANKING
PLATE
FAN REAR
OUTLET
EXTENTION
FAN SECURING
SCREW
FLUE HOOD
ASSEMBLY
KEYHOLE SLOT
FAN SECURING SCREW (4)
GASKETS
AND
SPACER
GASKET
SPACER
GASKET