Termination Boards for Tricon & Tricon CX G.M. International ISM0452-6
14
Supply:
24 Vdc nom (20 to 30 Vdc) reverse polarity protected, double terminal blocks for
redundant power supply, with OR diodes to mix supply voltages.
Max allowed current consumption: 1.5 A (as total supply).
Connection: by polarized plug-in disconnect screw terminal blocks to accommodate
terminations up to 2.5 mm
2
.
Protection fuse: 4 A time lag.
Fault detection:
The on-board diagnostic monitors both power supplies integrity and the module
cumulative fault. Any malfunction is reported by deactivating a solid-state relay and
activating the corresponding LEDs.
Alarm is issued if:
1) Power supply 1 or 2 < 17 Vdc or
2) Power supply 1 or 2 > 33 Vdc or
3) Module cumulative fault ON.
Alarm is removed if:
1) 20 Vdc < Power supply 1 and 2 < 30 Vdc and
2) No module cumulative fault.
Connection: by polarized plug-in disconnect screw terminal blocks to accommodate
terminations up to 2.5 mm
2
.
Output rating: 100 mA 35 V ( 1 V voltage drop)
I/O Card Interface:
Connection:
2 x ELCO 8016, 56 poles receptacle connector (require male mating connector).
Connector Keys: CON1, Large Key pos.5, Small Key pos.1.
CON2, Large Key pos.5, Small Key pos.1.
Cable: system cable 4000189-5xx.
HART Mux Interface:
Connection: 2 x 34-poles receptacle connector (require female mating connector).
Cable: flat cable CABF032.
Compatibility:
CE mark compliant, conforms to Directive:
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating: temperature limits – 40 to + 70 °C,
relative humidity max 90 % non condensing, up to 35 °C.
Max altitude: 2000 m a.s.l.
Storage: temperature limits – 45 to + 80 °C.
Safety Description:
ATEX: II 3G Ex ec IIC T4 Gc
IECEx: Ex ec IIC T4 Gc
Approvals:
IMQ 19 ATEX 073 X conforms to EN60079-0, EN60079-7.
IECEx IMQ 19.0013X conforms to IEC60079-0, IEC60079-7.
TUV Certificate No. C-IS-272994-01 SIL 3 conforms to IEC61508:2010 Ed. 2.
SIL 3 Functional Safety TÜV Certificate conforms to IEC61508:2010 Ed.2,
for Management of Functional Safety.
Mounting:
Hardware included for mounting on single DIN rail 35 mm.
Weight: about 700 g (excluding modules).
Location: installation in Safe Area or Zone 2, Group IIC T4.
Dimensions: Width 240 mm, Depth 180 mm, Height 154 mm.
General description:
This Termination Board with Enclosure (TBE) provides direct connection between
the I/O Card of the system and D5000 / D6000 Series modules.
The Intrinsically Safe protection and signal isolation between Safe and Hazardous Area,
is provided by D5000 Series Associated Apparatus. The 24 Vdc Power Supply of the
TBE is connected to two plug-in terminal blocks, for a redundant power supply.
The power supply for modules is given by TBE power bus.
Termination Board general characteristics:
Supported Tricon I/O Cards and D5000 / D6000 Series modules:
Refer to DTS0499 and DTS0885.
Functional Safety Management Certification:
G.M. International is certified by TUV to conform to IEC61508:2010
part 1 clauses 5-6 for safety related systems up to and included SIL3.
Functional Safety Applications:
Refer to Safety Manual ISM0472.
Number of positions Features
16
Power Supply voltage redundancy;
Abnormal supply voltage signaling;
Cumulative module fault signaling;
HART Multiplexing.
Termination Board 16 positions for
Tricon AI cards 3700, 3700A and 3721
Characteristics: Technical Data:
TBE-D5016-TRI-003 is a Termination Board supported by an aluminum shell suitable for
installation on EN/IEC60715 TH 35 DIN-Rail.
TBE-D5016-TRI-003 unit can be mounted with any orientation over the entire ambient
temperature range.
Electrical connections are the following:
ALARM, PWR1, PWR 2: polarized plug-in removable screw terminal blocks for
conductors up to 2.5 mm² (13 AWG) with a torque of 0.5-0.6 Nm.
CON1 SHIELD: screw terminal block for conductors up to 2 mm² (14 AWG) fully tight.
CON1: ELCO 8016, 56 poles connector with screws retaining method.
CON2 SHIELD: screw terminal block for conductors up to 2 mm² (14 AWG) fully tight.
CON2: ELCO 8016, 56 poles connector with screws retaining method.
J17 and J18 HART: 2 x 34 poles male connector.
Electrical connection can be plugged in/out into a powered unit without suffering or
causing any damage (for Zone 2 installations check the area to be nonhazardous
before servicing). Connect only one individual conductor per each clamping point. Use
only cables that are suitable for a temperature of at least 85°C.
Wiring has to be sized according to the current and the length of the cables. On the
section “Function Diagram” a block diagram identifies all connections.
Installation and wiring must be in accordance to the relevant national/international
installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas
atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)),
make sure that conductors are well isolated from each other and do not produce any
unintentional connection.
The unit shall be installed in an area of not more than pollution degree 2 according to EN/
IEC60664-1. When installed in EU Zone 2, the unit shall be installed in an enclosure that
provides a minimum ingress protection of IP54 in accordance with IEC 60079-0. The
enclosure must have a door or cover accessible only by the use of a tool. The end user is
responsible to ensure that the operating temperature of the module is not exceeded in the
end use application.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and
shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only
a cloth lightly moistened by a mixture of detergent in water.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit.
Any unauthorized card modification must be avoided.
According to EN/IEC61010, TBE-D5016-TRI-003 unit must be connected to SELV or
PELV supplies.
All circuits connected to TBE-D5016-TRI-003 unit must comply with the overvoltage
category II (or better) according to EN/IEC60664-1.
Image: