EasyManua.ls Logo

GMI Tricon - TB-D5016-TRI-010; TBE-D5016-TRI-010 Termination Boards; Product Overview and Technical Data; Installation and Safety Information; Mounting, Location, and Dimensions

Default Icon
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Termination Boards for Tricon & Tricon CX G.M. International ISM0452-6
39
Supply:
24 Vdc nom (20 to 30 Vdc) reverse polarity protected, double terminal blocks for
redundant power supply, with OR diodes to mix supply voltages.
Max allowed current consumption: 1.5 A (as total supply).
Connection: by polarized plug-in disconnect screw terminal blocks to accommodate
terminations up to 2.5 mm
2
.
2 LEDs indication: green color, one for supply 1 and one for supply 2.
Protection fuse: 3.15 A time lag.
I/O Card Interface:
Connection:
1 x SUB D50 male connector (require female mating connector).
Compatibility:
CE mark compliant, conforms to Directive:
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating: temperature limits – 40 to + 70 °C,
relative humidity max 90 % non condensing, up to 35 °C.
Max altitude: 2000 m a.s.l.
Storage: temperature limits – 45 to + 80 °C.
Safety Description:
ATEX: II 3G Ex ec IIC T4 Gc
IECEx: Ex ec IIC T4 Gc
UL: NI / I / 2 / ABCD / T4; C-UL: NI / I / 2 / ABCD / T4
EAC-EX: 2Ex ec IIC T4 Gc X
Approvals:
BVS 18 ATEX E 079 X conforms to EN60079-0, EN60079-7.
IECEx BVS 18.0066X conforms to IEC60079-0, IEC60079-7.
UL & C-UL E222308 conforms to UL 61010-1 and UL 121201 for UL and CAN/CSA
C22.2 No.61010-1-12 and CSA C22.2 No. 213 for C-UL.
ЕАЭС RU С-IT.AA87.В.00796/21 conforms to GOST 31610.0, GOST 31610.7.
TÜV Certificate No. C-IS-272994-01 SIL 3 conforms to IEC61508:2010 Ed.2.
SIL 3 Functional Safety TÜV Certificate conforms to IEC61508:2010 Ed.2,
for Management of Functional Safetyfety.
Mounting:
Hardware included for mounting on single DIN rail 35 mm.
Weight: about 700 g (excluding modules).
Location: installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4
or Class I, Division 2, Group A,B,C,D, T4.
Dimensions: Width 210 mm, Depth 170 mm, Height 154 mm.
General description:
This Termination Board (TB) with enclosure provides direct connection between
the I/O Card of the system and D5000 / D6000 Series modules.
The Intrinsically Safe protection and signal isolation between Safe and Hazardous Area,
is provided by D5000 Series Associated Apparatus. The 24 Vdc Power Supply of the TB
is connected to two plug-in terminal blocks, for a redundant power supply.
The power supply for modules is given by TB power bus.
Termination Board general characteristics:
Supported Tricon CX I/O Cards and D5000 / D6000 Series modules:
Refer to DTS0499 and DTS0811, DTS1491.
Functional Safety Management Certification:
G.M. International is certified by TUV to conform to IEC61508:2010
part 1 clauses 5-6 for safety related systems up to and included SIL3.
Functional Safety Applications:
Refer to Safety Manual ISM0385.
Number of positions Features
16 Power Supply voltage redundancy.
Termination Board 16 positions for
Tricon CX Universal card 3902X &
Analog Output card 3809X
Characteristics: Technical Data:
TB-D5016-TRI-010 / TBE-D5016-TRI-010 is a Termination Board supported by an
aluminum shell suitable for installation on EN/IEC60715 TH 35 DIN-Rail.
TB-D5016-TRI-010 / TBE-D5016-TRI-010 unit can be mounted with any orientation over
the entire ambient temperature range.
Electrical connections are the following:
PWR1 and PWR 2: polarized plug-in removable screw terminal blocks for conductors
up to 2.5 mm² (13 AWG) with a torque of 0.5-0.6 Nm.
M2: screw terminal block for conductors up to 2 mm² (14 AWG) fully tight.
CON1: SUB D50 connector with screws retaining method.
Electrical connection can be plugged in/out into a powered unit without suffering or
causing any damage (for Zone 2 installations check the area to be nonhazardous
before servicing). Connect only one individual conductor per each clamping point.
Use only cables that are suitable for a temperature of at least 85°C.
Wiring has to be sized according to the current and the length of the cables.
On the section “Termination Board Description” a block diagram identifies all connections.
Installation and wiring must be in accordance to the relevant national/international
installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas
atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)),
make sure that conductors are well isolated from each other and do not produce any
unintentional connection.
The unit shall be installed in an area of not more than pollution degree 2 according to
EN/IEC60664-1. When installed in EU Zone 2, the unit shall be mounted in a certified
Ex enclosure that provides a minimum ingress protection of IP54 in accordance with
EN/IEC60079-0. When installed in a Class I, Division 2 Hazardous Location, the unit shall
be mounted in a supplemental enclosure that provides a degree of protection not less
than IP54. The enclosure must have a door or cover accessible only by the use of a tool.
The end user is responsible to ensure that the operating temperature of the module is not
exceeded in the end use application.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and
shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only
a cloth lightly moistened by a mixture of detergent in water.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit.
Any unauthorized card modification must be avoided.
According to EN/IEC61010, TB-D5016-TRI-010 / TBE-D5016-TRI-010 unit must be
connected to SELV or PELV supplies.
All circuits connected to TB-D5016-TRI-010 / TBE-D5016-TRI-010 unit must comply with
the overvoltage category II (or better) according to EN/IEC60664-1.
Installation:
Image: