EasyManua.ls Logo

Goodman AMVC800805CX AA - Checking Primary Limit Control; Checking Auxiliary Limit Control

Goodman AMVC800805CX AA
53 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICING
34
SUPPLY
AIR
RETURN
AIR

3. Subtract the return air temperature from the supply air
temperature to determine the air temperature rise. Allow
adequate time for thermometer readings to stabilize.
4. Adjust temperature rise by adjusting the circulator
blower speed. Increase blower speed to reduce
temperature rise. Decrease blower speed to increase
temperature rise. Refer to Circulator Blower Speed
section in the Product Design section of this manual
for speed changing details. Temperature rise is related
to the BTUH output of the furnace and the amount of
air (CFM) circulated over the heat exchanger. Measure
motor current draw to determine that the motor is not
overloaded during adjustments.

Primary limit controls are nonadjustable, automatic reset,
bi-metal type limit control. Refer to the following drawing
for the location of the primary limit.
ENCLOSED DISK
FRONT VIEW SIDE VIEW

WARNING






1. Remove burner compartment door to gain access to
the primary limit.
2. Remove low voltage wires at limit control terminals.
3. With an ohmmeter, test between these two terminals as
shown in the following drawing. The ohmmeter should
read continuous unless heat exchanger temperature is
above limit control setting. If not as above, replace the
control.
COLOR
IDENTIFYING
TAB

4. After completing check and/or replacement of primary
limit control, reinstall burner compartment door.
5. Turn on electrical power and verify proper unit operation.
To aid in identifying these controls, refer to the Primary
Limit Charts in furnace Technical Manual for part number,
temperature setting and color(s) code.

The auxiliary limit control is designed to prevent furnace
operation in case of main blower failure in horizontal or
counterow installations. It may also open if the power
supply is interrupted while the furnace is ring.
The auxiliary limit control is suitable for both horizontal
right and horizontal left installations. Regardless of airow
direction, it does not need to be relocated. The (2) two
auxiliary limits are located on the blower housing (one on
each side), as shown in the following illustration.

Related product manuals