SERVICING
37

A/GMVC, A/GCVC model furnaces have factory installed
#45 natural gas orices.
The only time resizing is required is when a reduction in
ring rate is required for an increase in altitude or a furnace
is being converted for use with L.P. gas.
Orices should be treated with care in order to prevent
damage. They should be removed and installed with a box-
end wrench in order to prevent distortion. In no instance
should an orice be peened over and re-drilled. This will
change the angle or deection of the vacuum e󰀨ect or
entraining of primary air, which will make it di󰀩cult to adjust
the ame properly. This same problem can occur if an
orice spud of a di󰀨erent length is substituted.
WARNING

1. Check orice visually for distortion and/or burrs.
2. Check orice size by the number stamped on the orice.
A
GAS

The length of Dimension “A” determines the angle of Gas
Stream “B”.


GAS

A dent or burr will cause severe deection of the gas
stream.








Gas inlet and manifold pressures should be checked and
adjusted in accordance to the type of fuel being consumed.
The line pressure supplied to the gas valve must be within
the range specied below. The supply pressure can be
measured at the gas valve inlet pressure tap or at a hose
tting installed in the gas piping drip leg. The supply
pressure must be measured with the burners operating.
To measure the gas supply pressure, use the following
procedure.
WARNING


1. After turning off gas to furnace at the manual gas
shuto󰀨 valve external to the furnace, remove burner
compartment door to gain access to the gas valve.
2. Connect a calibrated water manometer (or appropriate
gas pressure gauge) at either the gas valve inlet
pressure tap or the gas piping drip leg as shown in the
following gures.




3. Turn ON the gas and electrical power supply and operate
the furnace and all other gas consuming appliances on
the same gas supply line.
4. Measure furnace gas supply pressure with burners ring.
Supply pressure must be within the range specied in
the following table.

 Minimum: 4.5” w.c. Maximum: 10.0” w.c.
Propane Gas Minimum: 11.0” w.c. Maximum: 13.0” w.c.
If supply pressure di󰀨ers from above, make necessary
adjustments to pressure regulator, gas piping size, etc.,
and/or consult with local gas utility.