SYSTEM OPERATION
7




1. Measure resistance between the neutral (white)
connection and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock
switch which interrupts unit voltage when the blower door is
opened for servicing. Do not defeat this switch.








1. Connect all necessary thermostat wires to the thermostat
connector on the furnace control (only available
connections on the furnace are R & C for power, Y for
Cooling Calls, W for Heating Calls, G for Fan Calls,
Dehum for Dehumidication Calls. Furnace will control
staging of indoor unit and outdoor unit automatically
based on these inputs).
2. Make sure thermostat is set to single stage heat / single
stage cool mode. When a cool call is given, 24VAC
should be applied to the Y terminal (G will have 24VAC
as well if a G wire is installed). When a heat call is given
24VAC should be applied to the W terminal (G may
have 24VAC as well if a G wire is installed). Even if a
heat pump is installed, do not setup the thermostat in
heat pump mode. Single stage heat / single stage cool
mode is all that is required for all applications. See rest
of manual for any exceptions. Do not setup thermostat
in multi stage mode either, it is not necessary.
3. For communicating 2 stage AC/HP or inverter AC/
HP outdoor units, connect the 1&2 wires between the
indoor and outdoor unit. It is recommended for 2 stage
applications that a separate transformer be installed in
the outdoor unit to provide 24VAC to the outdoor control.
R&C can be used between the indoor and outdoor in
2 stage AC application but only if there isn’t already a
transformer installed in the outdoor unit.
4. Turn on power to Indoor and Outdoor units
5. Charging outdoor unit: Provide a cooling call (Y or
Y+G) – this initial cooling call after the power is turned
on will run the outdoor unit at full capacity until the call
is removed. Use this mode for charging. If system is
running low stage cooling just cycle power and provide
a cool call again to ensure full capacity cooling.
6. System Testing: Download the CoolCloudHVAC phone
application (see pages 31 and 32)and use it to test all
operations of both indoor and outdoor units.
7. Conrm thermostat heat (W or W+G) and cool (Y or
Y+G) function properly and the system is turning on in
the correct mode. The internal algorithms will constantly
be adjusting the staging times / cooling capacities based
on load changes to the space.







The furnace contains internal logic to control equipment
staging. An adjustable target runtime is available (range
from 1 to 240 minutes) and set through the appropriate
system menu. The system will constantly be adjusting
staging in an e󰀨ort to satify the thermostat call for cooling
(Y only) or heating (W Only) as close to the set target
runtime as possible. See information below for setting
options.

There are 6 options available in the Comfort Setting
Menu which impacts both the System Target Runtime and
Dual Fuel Operation. Dual Fuel operation adjustments
only apply if a communicating heat pump is installed.
Comfort Setting Options 1 – 5 have set values for the
System Target Runtime and option 6 enables additional
menus to customize all comfort settings. See list below
for the System Target Run times associated with the rst
5 Comfort Settings. These rst 5 options are setup to
help satisfy the thermostat slower or faster based on the
selection where option 1, with a 10 minute Target Runtime,
is attempting to satisfy much faster than option 5, with a 30
minute Target Runtime.

Comfort Setting Option 1) 10 Minute System Target
Runtime
Comfort Setting Option 2) 15 Minute System Target
Runtime
Comfort Setting Option 3) 20 Minute System Target
Runtime
Comfort Setting Option 4) 25 Minute System Target
Runtime
Comfort Setting Option 5) 30 Minute System Target
Runtime