BLOWER PERFORMANCE DATA
26
0.1" 0.2" 0.3" 0.4" 0.5"
High 1,155 1,090 1,025 950 895
ATUF182416 Med. 875 830 790 750 715
Low 640 610 570 535 490
High 1,135 1,085 1,025 965 915
ATUF193116 Med. 860 825 780 750 680
Low 600 570 545 500 465
High 1,455 1,385 1,330 1,205 1,090
ATUF303016 Med. 1,340 1,290 1,230 1,140 1,050
Low 1,075 1,030 980 910 840
High 1,345 1,290 1,230 1,150 1,070
ATUF363616 Med. 1,270 1,210 1,140 1,075 980
Low 1,045 1,005 955 885 805
High 1,700 1,680 1,645 1,610 1,535
ATUF364216 Med. 1,500 1,480 1,440 1,380 1,325
Low 135 1,320 1,275 1,230 1,195
High 2,065 2,000 1,925 1,860 1,780
ATUF374316
Med. 1,685 1,635 1,550 1,470 1,410
Low 1,490 1,425 1,345 1,280 1,205
High 2,135 2,080 1,985 1,900 1,805
ATUF486016
Med. 1,975 1,935 1,875 1,775 1,675
Low 1,715 1,670 1,650 1,590 1,530
CFM deliverd against External Static Pressure
Model Speed
ATUF
Note: Assumes dry coil with filter in place; SCFM correction for wet coil = 4% (208V/240V)