SERVICING
52
E
CEC EECRC ER
ERE ERC R .
Use adapter kit #0151K00000S to measure gas
pressure on White-Rodgers 36J54 gas valves.
Only small variations in gas pressure should be made by
adjusting the gas valve pressure regulator. The manifold
pressure must be measured with the burners operating. To
measure and adjust the manifold pressure, use the following
procedure.
external to the furnace.
3. Outlet pressure tap connections: White-Rodgers 36J54
valve: Back outlet pressure test screw (inlet/outlet
pressure tap) out one turn (counterclockwise, not more
than one turn).
4. Attach a hose and manometer to outlet pressure tap.
5. Turn ON the gas supply.
It is recommended that the CoolCloud phone application be
used for all functional tests. If a manual test is preferred there
are two methods available.
1. Using the on board push button switches, enter the
Gas Pressure Test menu (7 segment display “gPt”) and
select YES to enable the Gas Pressure Test. The system
terminated by pressing any of the 3 on board push button
switches.
2. If installing a communicating fossil fuel system, make
sure the 1,2,R,C terminal is either removed or there are
no wires connected. If utilizing an accessory module to
control a non-communicating heat pump, disconnect the
RJ12 jack from the furnace.
3. Provide power to the furnace.
4. Provide a thermostat W call. The system will continuously
5. When test is complete, remove the W (heat) call to the
furnace. The system will shut down.
2. If installing a communicating fossil fuel system, make
sure the 1,2,R,C terminal is either removed or there are
no wires connected. If utilizing an accessory module to
control a non-communicating heat pump, disconnect the
RJ12 jack from the furnace.
3. Provide power to the furnace.
4. Provide a thermostat W call and allow furnace to begin
its ignition sequence.
5. Remove thermostat W call and allow furnace to enter idol
state (7 segment display IdL).
6. Provide the thermostat W call again. The furnace will now
operate in low stage for greater than 5 minutes (assuming
the target run time has been set to something greater than
10 minutes).
7. When test is complete, remove the W (heat) call to the
furnace. The system will shut down.
M
a
no
m
e
t
er
M
a
n
o
m
e
t
e
r
H
o
s
e
High Fire Regulator
Adjust
Regulator
Vent
O
n
/O
f
f S
w
i
tc
h
H
ig
h
Fi
re
C
oi
l
T
e
rm
i
na
l
(
H
I)
C
o
a
x
i
al
C
o
il
Te
r
m
in
a
l
(
M
)
Common
Terminal(C)
White-Rodgers Model 36J54 Connected to Manometer
3.5
E
CEC EECRC ER
ERE ERC R .
High Stage 3.2 to 3.8" w.c. 3.5" w.c.
Low Stage
1.6 to 2.2" w.c. 1.9" w.c.