SERVICING
30
3. Turn ON the gas and electrical power supply and operate
the furnace.
4. Measure gas manifold pressure with burners ring. Adjust
manifold pressure using the table below.
2.8 -3.2" w.c.
The nal manifold pressure must not vary from the above
specied pressures. Any necessary major changes in gas ow
rate should be made by changing the size of the burner orice.
5. White-Rodgers 36J22 Valves:
a. Back outlet pressure test screw (inlet/outlet pressure
boss) out one turn (counterclockwise, not more than
one turn).
b. Attach a hose and manometer to the outlet pressure
outlet pressure boss.
c. Turn ON the gas supply.
d. Turn on power and close thermostat “R” and “W”
contacts to provide a call for low stage heat.
e. Measure the gas manifold pressure with burners ring.
Adjust manifold pressure using the Manifold Gas
Pressure table shown below.
f. Remove regulator cover screw from the outlet pressure
regulator adjust tower and turn screw clockwise to
increase pressure or counterclockwise to decrease
pressure. Replace regulator cover screw.
i. Turn o all electrical power and gas supply to the
system.
j. Remove the manometer hose from the hose barb tting
or outlet pressure boss.
k. Turn outlet pressure test screw in to seal pressure port
(clockwise, 7 in-lb minimum).
I
VE
ISE
EERIWER SUS
SUERESERVII RISI ISUI
M
UIE WERSURES M E RESE
IURE
SM USERER MEERSIJURRE
6. Turn on gas to furnace and check for leaks. If leaks are
found, repair and then reinstall burner compartment door.
7. Turn on electrical power and verify proper unit operation.
Pressure Regulator
Adjustment
(Under Cap Screw)
Gas Valve
On/Off
Selector
Switch
INLET
OUTLET
Inlet Pressure
Tap
Outlet Pressure
Tap
IVE
ISEEERIWERSU SSU
ERE SERVIIRISI
ISE
WER ERE SERVII
- ULN furnaces use a 120V
silicone nitride igniter, part #0130F00717. The normal
operating temperature is approximately 2156°F - 2678°F. At
room temperature the igniter ohm reading should be from
20-100 ohms.
IE VE W RESE
The 96% ULN products utilize a pressure transducer. The
pressure transducer signals the control board to modulate the
heating cycle during a call for heat by regulating the induced
draft motor speed. By regulating the speed of the induced
draft motor, proper air-fuel ratios are maintained.
Sensing range specication: 0.0-2.0 inches W.C.
Voltage specications:
• Steady State: 5.0 vDC from red to green wire (transducer
wiring harness input)
• With Inducer o: 0.25 vDC from black to green wire
(transducer wiring harness output).
• During operation: Output range equals 0.25 - 4.0 vDC
Potential errors:
1. Control board does not receive 0.25 vDC for inducer motor
with motor o
a. Will result in 2-ash error code on the control board
2. Control board does not receive the required voltage
change (0.25 - 4.0 vDC) during inducer motor operation.
a. Will result in 3-ash error code on the control board